CHAPTER 5: SETTINGS
SYSTEM SETUP
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-171
5
PMU 1 SIGNAL SOURCE:
SRC 1
Range: available signal sources
PMU 1 CLASS:
M-CLASS
Range: None, M-CLASS, P-CLASS
PMU 1 FORMAT:
Integer
Range: Integer, Floating-point
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
PMU 1 RATE:
10/sec
Range: 1, 2, 4, 5, 10, 12, 15,20, 25, 30,50, 60, 100, 120
/sec
PMU 1 f & df/dt
FILTER: None
Range: None, 10Hz/s <10Hz, 10Hz/s <20Hz, 20Hz/s
<10Hz, 20Hz/s <20Hz
C37.118 PMU 1
CONFIGURATION
See below
PMU 1 PHS- 1:
Off
Range: available synchrophasor values
PMU 1 PHS-14:
Off
Range: available synchrophasor values
PMU 1 PHS- 1:
NM: GE-UR-PMU-PHS 1
Range: 16-character ASCII string
PMU 1 PHS-14:
NM: GE-UR-PMU-PHS 14
Range: 16-character ASCII string
PMU 1 A-CH- 1:
Off
Range: available FlexAnalog values
PMU 1 A-CH-8:
Off
Range: available FlexAnalog values
PMU 1 A-CH- 1:
NM: AnalogChannel 1
Range: 16-character ASCII string
PMU 1 A-CH-8:
NM: AnalogChannel 8
Range: 16-character ASCII string
PMU 1 D-CH- 1:
Off
Range: available FlexLogic operands
PMU 1 D-CH-16:
Off
Range: available FlexLogic operands
PMU 1 D-CH- 1
NM: Dig Channel 1
Range: 16-character ASCII string
PMU 1 D-CH-16
NM: Dig Channel 16
Range: 16-character ASCII string
PMU 1 D-CH- 1
NORMAL STATE: Off
Range: Off, On
PMU 1 D-CH-16:
NORMAL STATE: Off
Range: Off, On