Technical Manual
KVCG202/EN M/H11
KVGC202
6.4.5
Overvoltage detection (V>)
The overvoltage detector will block operations that raise the voltage, to prevent excessive
voltage on busbars local to the transformer.
V> output relay allocated in the relay mask will pick up the overvoltage detection
condition to give the alarm indication.
The pick-up/drop-off differentials on the overvoltage detector will be –1% of the threshold
setting.
6.4.6
Circulating current detection (
I
c>)
The circulating detector (
I
C>) limits the tap differences between parallel transformers. In
the event of excessive circulating current over a certain period (t
I
C), the
I
c detector will
be used to internally block the relay for both ‘Raise’ and ‘Lower’ operations.
I
c> output relay allocated in the relay mask will pick up the excessive circulating current
condition to give the alarm indication. If the logic link [LOG2] is set to ‘1’,
the alarm condition will also cause the blocking of the tap change control operation.
The pick-up/drop-off differentials on the excessive circulating current is –5% of the
threshold setting.
6.4.7
Overcurrent detection (
I
L>)
If the load current (
I
L) through a transformer exceeds the threshold setting,
I
L> output
relay allocated in the relay mask will pick up the excessive load current condition to give
the alarm indication. If the logic link [LOG3] is set to ‘1’, the operation of tap changer will
be inhibited for fault or overload current through the transformer.
The pick-up/drop-off differentials on the overcurrent detector is –5% of the threshold
setting.
6.4.8
Undercurrent detection (
I
L<)
If the load current (
I
L) through a transformer drops below the threshold setting,
I
L<
output relay allocated in the relay mask will pick up the insufficient load current condition
to give the alarm indication. If the logic link [LOG8] is set to‘1’, the operation of tap
changer will be inhibited. The pick-up/drop-off differentials on the undercurrent detector
is +5% of the threshold setting.
6.4.9
Reverse current blocking (
I
rev)
If the load current
I
L) is in reverse direction,
I
rev output relay allocated in the relay mask
will pick up the reverse current condition to give the alarm indication. If the logic link
[LOG6] is set to ‘1’, the operation of tap changer will be inhibited and the delay timer will
be reset instantaneously.
If the system link (SD6) is set to ‘1’ then the relay will use group 2 settings.
6.4.10
Run-Away
Run-Away is the feature that monitors the tap position and checks that an authentic tap
change signal has been initiated. An alarm is initiated if:
-
tap changer operates in the absence of an initiation signal or
-
tap changer operates in a direction which causes the voltage to move further away
from the desired voltage Vs.
Blocking condition is initiated to inhibit any further tap changes if logic link [LOG7] is set
to ‘1’.
Summary of Contents for KVGC 202
Page 2: ......
Page 10: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 122: ...KVCG202 EN M H11 Technical Manual KVGC202 Figure 36 Test circuit diagram ...
Page 123: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 1 ...
Page 124: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 125: ...Technical Manual KVCG202 EN M H11 KVGC202 Figure 37 Relay inverse time characteristic curve ...
Page 126: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 127: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 2 ...
Page 128: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 129: ...Technical Manual KVCG202 EN M H11 KVGC202 ...
Page 130: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 131: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 3 ...
Page 132: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 133: ...Technical Manual KVCG202 EN M H11 KVGC202 W02474 10 KVGC202 00 SHEET 1 ...
Page 134: ...KVCG202 EN M H11 Technical Manual KVGC202 W02475 10 KVGC202 00 SHEET 2 ...
Page 135: ...Technical Manual KVCG202 EN M H11 KVGC202 W02476 10 KVGC202 00 SHEET 3 ...
Page 136: ...KVCG202 EN M H11 Technical Manual KVGC202 W02477 10 KVGC202 00 SHEET 4 ...
Page 137: ...Technical Manual KVCG202 EN M H11 KVGC202 W02478 10 KVGC202 00 SHEET 5 ...
Page 138: ...KVCG202 EN M H11 Technical Manual KVGC202 W02479 10 KVGC202 01 SHEET 1 ...
Page 139: ...Technical Manual KVCG202 EN M H11 KVGC202 W02480 10 KVGC202 01 SHEET 2 ...
Page 140: ...KVCG202 EN M H11 Technical Manual KVGC202 W02481 10 KVGC202 01 SHEET 3 ...
Page 141: ...Technical Manual KVCG202 EN M H11 KVGC202 W02482 10 KVGC202 01 SHEET 4 ...
Page 142: ...KVCG202 EN M H11 Technical Manual KVGC202 W02483 10 KVGC202 01 SHEET 5 ...
Page 143: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 4 ...