Technical Manual
KVCG202/EN M/H11
KVGC202
3.3.4
Menu columns
Col No
Heading
Description
00
SYSTEM DATA
Settings and data for the system – relay and serial
communications.
01
STATUS
Settings for tap control modes
02
MEASURE
Display of directly measured and calculated quantities
03
CONTROL 1
Settings for group 1 miscellaneous control functions
04
LOGIC 1
Settings for group 1 miscellaneous logic functions
05
CONTROL 2
Settings for group 2 miscellaneous control functions
06
LOGIC 2
Settings for group 2 miscellaneous logic functions
07
INPUT MASKS
User assigned allocation of logic input
08
RELAY MASKS
User assigned allocation of output relays
The menu cells that are read only are marked
[READ]
Cells that can be set are marked
[SET]
Cells that can be reset are marked
[RESET]
Cells that are password protected are marked
[PWP]
3.3.5
System data
Cell
Text
Status
Description
0000
SYSTEM DATA
READ
Column heading
0002
Password
PWP
Password that must be entered before certain settings
may be changed
0003
SD Links
PWP
Function links that enable the user to enable (activate)
the options required
0
1
Rem Cntrl
1= enable remote control
2
Rem LSB
1= enable remote load shedding/boosting
3
Rem Grp2
1= enable remote change to group 2 setting
4
En Grp2
1= enable group two settings; 0 = hidden
5
1=Grp2
1= select group 2 settings
6
I
rev=Grp 2
1= enable reverse current select group 2 settings
7
Log Evts
1= enable logic changes in event records
8
9
Extrn V
1= TPI uses external V ref; 0=TPI uses system voltage
0004
Description
PWP
Product description – user programmable text
0005
Plant Ref.
PWP
Plant reference – user programmable text
0006
Model
READ
Model number that defines the product
0008
Serial No.
READ
Serial number – unique number identifying the
particular product
0009
Freq
SET
Default sampling frequency - must be set to power
system frequency
000A
Comms Level
READ
Indicates the Courier communication level supported
by the product
000B
Rly Address
SET
Communication address (1 to 255)
000C
Plnt Status
READ
Binary word, used to transport plant status information
over communication network
Summary of Contents for KVGC 202
Page 2: ......
Page 10: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 122: ...KVCG202 EN M H11 Technical Manual KVGC202 Figure 36 Test circuit diagram ...
Page 123: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 1 ...
Page 124: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 125: ...Technical Manual KVCG202 EN M H11 KVGC202 Figure 37 Relay inverse time characteristic curve ...
Page 126: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 127: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 2 ...
Page 128: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 129: ...Technical Manual KVCG202 EN M H11 KVGC202 ...
Page 130: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 131: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 3 ...
Page 132: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 133: ...Technical Manual KVCG202 EN M H11 KVGC202 W02474 10 KVGC202 00 SHEET 1 ...
Page 134: ...KVCG202 EN M H11 Technical Manual KVGC202 W02475 10 KVGC202 00 SHEET 2 ...
Page 135: ...Technical Manual KVCG202 EN M H11 KVGC202 W02476 10 KVGC202 00 SHEET 3 ...
Page 136: ...KVCG202 EN M H11 Technical Manual KVGC202 W02477 10 KVGC202 00 SHEET 4 ...
Page 137: ...Technical Manual KVCG202 EN M H11 KVGC202 W02478 10 KVGC202 00 SHEET 5 ...
Page 138: ...KVCG202 EN M H11 Technical Manual KVGC202 W02479 10 KVGC202 01 SHEET 1 ...
Page 139: ...Technical Manual KVCG202 EN M H11 KVGC202 W02480 10 KVGC202 01 SHEET 2 ...
Page 140: ...KVCG202 EN M H11 Technical Manual KVGC202 W02481 10 KVGC202 01 SHEET 3 ...
Page 141: ...Technical Manual KVCG202 EN M H11 KVGC202 W02482 10 KVGC202 01 SHEET 4 ...
Page 142: ...KVCG202 EN M H11 Technical Manual KVGC202 W02483 10 KVGC202 01 SHEET 5 ...
Page 143: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 4 ...