Technical Manual
KVCG202/EN M/H11
KVGC202
5.1.5
Tap pulse duration (tPULSE)
The tap pulse duration can be set between 0.5 to 5 seconds. It is initiated to ‘Raise volts’
or ‘Lower volts’ during multiple tap change sequence.
5.1.6
Line drop compensation (Vr and Vxl)
The resistive and reactive controls are set such that the voltage at a point remote to the
tap changing transformer can be regulated for varying load conditions.
The resistive line drop compensation can be set between 0 and 50 volts at rated current.
The reactive line drop compensation can be set between -50 to +50 volts at rated current.
Vr =
3.Ip.RL
VT ratio
Vr =
3.Ip.XL
VT ratio
Where
Ip
= primary rated current of line CT
RL
= resistive component of line impedance
XL
= reactive component of line impedance
VT ratio= ratio of primary to secondary voltages of line VT
Setting the Vxl to –ve value allows selection of reverse reactance for control of circulating
current where transformers are connected in parallel. For reverse reactance control the
settings are now as below:
Vxl (reverse) =
3.Ip.Xt
VT ratio
Where Xt
= reactance of transformer
Now Vr =
3.Ip
VT ratio
(RL Cos
φ
+ XL Sin
φ
+ Xt Sin
φ
Where Cos
φ
= power factor of load
Note :
The setting PF angle setting in the control column should be set to
(Cos
φ
) in this case.
The above shows that the effective Vr compensation can vary significantly for varying
power factors. Reverse reactance control of parallel transformers is used where
transformers are dissimilar or at different locations and the power factor variation is not
too great.
5.1.7
Circulating current compensation (Vc)
An alternative method of achieving stable control of parallel transformers is to minimise
the reactive circulating current
I
c by the introduction of a parallel compensation voltage
Vc, which is proportional to
I
c. To establish the value of
I
c, a pair of pilots must be
connected between the KVGC’s on the parallel transformers (see Figure 2 in Appendix
3).
The Vc setting can be set between 0 and 50 volts for reactive rated current applied to the
circulating current inputs. The Vc setting is determined during commissioning procedures
such that optimum stability is obtained for parallel transformers.
An approximate setting is given by:
Vc =
3.Ip.Xt
VT ratio
Circulating current control using Vc setting allows both resistive and reactive components
of line drop compensation to be utilised and is independent of power factor variations.
Summary of Contents for KVGC 202
Page 2: ......
Page 10: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 122: ...KVCG202 EN M H11 Technical Manual KVGC202 Figure 36 Test circuit diagram ...
Page 123: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 1 ...
Page 124: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 125: ...Technical Manual KVCG202 EN M H11 KVGC202 Figure 37 Relay inverse time characteristic curve ...
Page 126: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 127: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 2 ...
Page 128: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 129: ...Technical Manual KVCG202 EN M H11 KVGC202 ...
Page 130: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 131: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 3 ...
Page 132: ...KVCG202 EN M H11 Technical Manual KVGC202 ...
Page 133: ...Technical Manual KVCG202 EN M H11 KVGC202 W02474 10 KVGC202 00 SHEET 1 ...
Page 134: ...KVCG202 EN M H11 Technical Manual KVGC202 W02475 10 KVGC202 00 SHEET 2 ...
Page 135: ...Technical Manual KVCG202 EN M H11 KVGC202 W02476 10 KVGC202 00 SHEET 3 ...
Page 136: ...KVCG202 EN M H11 Technical Manual KVGC202 W02477 10 KVGC202 00 SHEET 4 ...
Page 137: ...Technical Manual KVCG202 EN M H11 KVGC202 W02478 10 KVGC202 00 SHEET 5 ...
Page 138: ...KVCG202 EN M H11 Technical Manual KVGC202 W02479 10 KVGC202 01 SHEET 1 ...
Page 139: ...Technical Manual KVCG202 EN M H11 KVGC202 W02480 10 KVGC202 01 SHEET 2 ...
Page 140: ...KVCG202 EN M H11 Technical Manual KVGC202 W02481 10 KVGC202 01 SHEET 3 ...
Page 141: ...Technical Manual KVCG202 EN M H11 KVGC202 W02482 10 KVGC202 01 SHEET 4 ...
Page 142: ...KVCG202 EN M H11 Technical Manual KVGC202 W02483 10 KVGC202 01 SHEET 5 ...
Page 143: ...Technical Manual KVCG202 EN M H11 KVGC202 APPENDIX 4 ...