Intellix
™
BMT 330 User Manual
Page 46
BMT330UM
v1.0
20-Jun-16
Relay Control
Figure 17: Alarm Statuses tab
The
Relay Control
tab provides the means to control the Intellix™ BMT 330 relays. By
default the
Active relay on alarm
is enabled. Thus the relays reflect the alarm
statuses:
Relay 1 (Service) is energized by default. If a service alarm is on or Intellix™
BMT 330 loses power it will switch to OFF.
Relay 2 (Warning) and Relay 3 (Alarm) are de-energized by default. If either of
their respective alarms is on, the corresponding relay will switch to ON.
Relays can be manually controlled by disabling the
Active relay on alarm
. Then the
relays are not synchronized with the alarm statuses; and the user can manually
switch the relays (by clicking on the relay switch icon and then click on
Write/Program
).
NOTE: disabling the
Active relay on alarm
is used to install/test the relays wiring.
During operation Intellix™ BMT 330 requires it to be enabled; otherwise any service,
warning and/or alarm event will not reflect on the relays.