Page 43
Intellix
™
BMT 330 User Manual
BMT330UM
v1.0
20-Jun-16
PD data alarm
Description
Primary Phase B – PDI Polar Plot
Trend Status
The PDI change for Primary B in the polar plot is
above a given threshold (see Period to calculate
PD trend, PDI trend warning and PDI trend alarm
in Table 4)
Primary Phase C – PDI Polar Plot
Trend Status
The PDI change for Primary C in the polar plot is
above a given threshold (see Period to calculate
PD trend, PDI trend warning and PDI trend alarm
in Table 4)
Bushing data alarms
The following warnings/alarms may be triggered by bushing monitoring events.
Bushing data alarm
Description
Primary Phase A – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Primary A (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)
Primary Phase B – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Primary B (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)
Primary Phase C – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Primary C (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)
Secondary Phase A – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Secondary A (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)
Secondary Phase B – C1% Polar
Plot Level Status
The C1% polar plot amplitude is above a given
threshold on an area defined by Secondary B (see
C1% Polar plot level warning and C1% Polar plot
level alarm in Table 5)