GE IJS51A Instructions Manual Download Page 19

SYNCHRONISM-CHECK  RELAYS 

TYPE 

INTRODUCTION 

The  Type  IJS  relays  are  of  the  induction-disk 

construction  and  are  intended  for  use  as  synchro­

nism-check relays. 

These  relays  have  two  shaded-pole  U-magnet 

driving-elements  acting  on  opposite  sides  of  a 

single  rotating  disk. 

(See  Fig.  2 )   One  of these, 

the operating element, drives  the disk in the contact­

closing  direction,  and  the  other  the  restraining 

element,  drives  the  disk  in  the  opposite  direction. 

The  disk  shaft  if  restrained  by  a  spiral  spring, 

the purpose  being to hold the  contacts  open  when the 

relay  is  de-energized.  The  motion  of  the  disk is 

retarded  by  permanent  magnets  (drag  magnets) 

acting  on the  disk to  give a  time delay. 

The  Type  IJS5 1A  relay  has  a  seal-in  unit 

mounted  to the  left  of the  disk shaft,  which  operates 

when the  main contacts  close. 

The  Type  IJS52A  relay  does  not  have a  seal-in 

unit  and  is  used  primarily  as  an  auxiliary  to  the 

Type  GES  Synchronizing  relay  as  described below. 

APPLICATION 

The  Type  IJS  relay  is applicable as a  synchro­

nism-check  relay  to  permit  closure  of  a  circuit 

breaker  only  when  the  frequency  difference  is 

negligible  or  is  zero  due  to  the  two sources which 

energize  it being interconnected  elsewhere. 

The IJS51A  should be used where a target-seal­

in  unit  is  required;  otherwise  use  the  IJS52A. 

In 

such  an  application  the  voltages  may  be 

considerably out of phase due  to load transfer around 

the  loop  which  is  open  at  the  breaker  controlled 

by  the relay.  Forms  of the relay are  available with 

a  rated  calibration  range  up  to 60 degrees; but for 

settings  over  20  degrees  consideration  should  be 

given  to  t�1e  resulting  generator  stresses  at  the 

instant  of  closure  through  existing  system  im­

pedances,  as  in  any  other  situation  involving  out­

of-phase  closure. 

On  systems  where  the  two  sides  of  a  given 

breaker  may  or  may  not  be  interconnected  else ­

where  at  any  given  moment  when  paralleling  is 

desired,  the  GES  or  GXS  is  used  for  synchronizing 

when  a  finite  frequency  difference  exists;  and  the 

IJS  is  used  at  the  same  location  for  synchronism 

IJS 

check  when  the  frequency  differenc e  is  negligible 

or  zero  due  to  the  existance  of  an interconnection 

elsewhere. 

In 

this application,  the  IJS contacts  are 

connected  in  parallel  with  those  of  the  GES  or 

GXS. 

The  IJS  is  not  adaptable  to  applications  in­

volving  continuous  loading  of  the  contact  circuit, 

since  contact  welding  may  result  even  with contact 

loadings  that  are  low  in relation to  the  interrupting 

capacity  of  the  contacts. 

The  control  should  be 

designed to  energize  the IJS coils  when synchronism 

is  to  be  checked;  and  to  permit  the  IJS  contacts 

to  be  the  last  to  complete  a  closing  c ircuit which 

is promptly  bypassed  or  interrupted. 

Cross  feed  from  the  energized  side  to  the  de­

energized  side  is  very  low,  because  the  operating 

principle  of  the  relay  requires  the  two  windings 

on  the  operating  magnet  to  be  additive while those 

on  the  restraining  magnet  are  subtractive,  and, 

therefore,  the  coupling  from  the  bus  side  to  the 

line  side coil  on the  operating  magnet  is practically 

cancelled  by  the  reverse  polarity  of  the  corres­

ponding  coupling between the  coil  on  the restraining 

magnet . 

OPERATING  CHARACTERISTICS 

The  operating  coils,  mounted  on  the  left-hand 

side,  produce  a  torque  tending  to  close  the  relay 

contacts.  This  torque  is proportional  to the  vector 

sum  of  the  voltages  whose phase positions  are  being 

compared. 

The  torque  produced  by  the  restraint 

coils  is  proportional  to  the  vector  difference  of 

the  voltages. 

The  operating  torque  is  maximum 

when  the  systems  are  in  synchronism  ami  is  zero 

when  they  are  in  phase  opposition;  the  reverse 

is true of the restraining torque. 

The  closing  angle  of  the  relay  is  defined  as 

the  maximum  phase  displacement  of  the two voltages 

at  which  the  relay  will  close  its  contacts  when 

the  voltages  are  at  rated  value.  The  20-degree 

closing  angle  is  considered  standard;  however, 

other  settings  may  be  made  as  indicated  by  the 

voltage-phase  angle  characteristics  shown  in  Fig. 1. 

These  instructions  do  not  purport  to  cover  all  details  or  variations  in  equipment  nor  to  p rovide  for 

every  possible  contingency  to  be  met  in  connection  with  installation,  operation  or  maintenance. 

Should 

further  information  be  desired  or  should  particular  problems  arise  which  are  not  covered  sufficiently  for 
the  purchaser's  purposes,  the  matter  should  be  referred  to  the  General  Electric  Company. 

To  the  extent  required  the  products  described  herein  meet  applicable  ANSI,  IEEE  and  NEMA  standards; 

but  no  such  assur ance  is  given  with  respect  to  local  codes  and  ordinances  because  they  vary  greatly. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for IJS51A

Page 1: ...Types IJS51A and IJS52A INSTRUCTIONS SYNCHRONISM CHECK RELAYS GEH 179111 GE Meter and Control 205 Great Valley Parkway Malvern PA 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ...ENS 6 CONSTRUCTION 6 RECEIVING HANDLING AND STORAGE 6 ACCEPTANCE TESTS 7 INSTALLATION PROCEDURE 7 PERIODIC CHECKS AND ROUTINE MAINTENANCE 8 SERVICING 9 Closing Angle Adjustment 9 Time Characteristics 10 RENEWAL PARTS 10 Cover Photo 8007016 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 3: ... be considerably out of phase due to load transfer around the loop that is open at the breaker controlled by the relay Forms of the relay are available with a rated calibration range up to 600 but for settings over 200 consideration should be given to the resulting generator stresses at the instant of closure through existing system impedances as in any other situation involving out of phase closu...

Page 4: ...le is considered standard however other settings may be made as indicated by the voltage phase angle characteristics shown in Figure 1 The time delay characteristics of the Type IJS relay are obtained primariy by the time dial setting The time dial controls the distance the contacts must travel before closure and hence controls the time delay At No 10 time dial setting the travel is maximum wherea...

Page 5: ... from 0 2 up to 2 0 amperes at the minimum control voltage If this tap is used with circuits requiring more than 2 amperes there is a possibility that the 7 ohm resistance will reduce the current to so low a value that the proper current may not be obtained The 2 0 ampere tap should be used with circuits that take 2 0 amperes or more at minimum control voltage provided the current does not exceed ...

Page 6: ...e connection plugs have been inserted The relay case is suitable for either semi flush or surface mounting on all panels up to 2 inches thick and appropriate hardware is available However panel thickness must be indicated on the relay order to ensure that proper hardware will be included For outline and drilling dimensions see Figure 15 RECEIVING HANDLING AND STORAGE These relays when not included...

Page 7: ...tact when the time dial is set at 0 The contact wipe should be approximately 1 3211 3 Check that the control spring is not deformed and that the spring convolutions at No 5 time dial setting are reasonably concentric ELECTRICAL TESTS Connect the relay as shown in Figure 11 and check the following 1 Check that with at least 115 volts 60 cycle single phase source connected to both operating coils th...

Page 8: ...o studs 5 6 is adjusted until the synchronizing check unit just closes its contact The difference between the two voltages should agree approximately with the voltage given on the curve shown in Figure 14 for the phase angle used i e 24 volts for 200 closing When using connections shown in either Figure 11 or Figure 13 check the operating time at 0 displacement with 115 volts on each coil using th...

Page 9: ...hould be approximately centered between the poles of the U magnet and drag magnet ELECTRICAL ADJUSTMENTS Closing Angle Adjustment Connect the relay as shown in Figure 11 To make an accurate adjustment of the closing angle a phase shifter and phase angle meter are required along with a means for voltage control Two adjustments are necessary for obtaining a desired closing angle adjustable resistor ...

Page 10: ...ficient quantities of renewal parts should be kept in stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sales Office of the General Electric Company Specify the name of the part wanted quantity required and complete nameplate data including the serial number of the relay If possible give the General Electric requisition number o...

Page 11: ...nts with Rated Voltage Maintained on One Circuit CONNECTING PLUG AUXIL IARY BRUSH BLOCK TERMINAL BLOCK SHORTING BAR NOTE AF TER ENGAG ING AUXIL IARY BRUSH CONNECTING PLUG TRAVELS 1 4 INCH BEFORE ENGAG ING THE MAIN BRUSH ON THE TERMINAL BLOCK Figure 2 8025039 Cross Section of Drawout Case Showing Position of Auxiliary Brush and Shorting Brush 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Page 12: ...ic of 60 Cycle Relay 12IJS51A1 With Rated Voltage On Both Circuits With 10 Time Dial Settings Figure 4 8007013 Type IJS51A Relay Unit in Cradle Rear View 9 1 8 1 u J en _ 7 w I 6 0 0 0 0 0 0 50 en 0 z 8 4 w en w 3 I z 2 w a 0 0 0 0 10 0 I i I I c I i lfzo CLOSING ANGLE i I J30 CLOSING ANGLE i I I I j 1 l I u 4 0 gw G v 1 v I i f I f i 1 v J I I v I __ _ V 6oo CLOSING ANGLE i J I 50 40 30 20 10 0 1...

Page 13: ...age on Both Circuits With 10 Time Dial Settings Sl OUND _j SHADING COILS t l I 1 2 l l 5 6 l 7 I8 OOT REST SHORT F I NGER Figure 9 6305898 3 Internal Connec tions For Type IJS51A Relay Front View I 20 16 12 V 0 0 u I II 8 v 4 v ov 2 i 1 I v I v I v I I I 4 6 TilliE DIAl SETTING i v v 8 10 Figure 8 6400150 2 Operating Time of Type IJS Relay With 200 Closing Angle Time at oo 115 Volts 60 Cycles on B...

Page 14: ... G CIRCUIT OF oi Hl DEVICE FUNCTION NUMBERS 25 SYNCHRONISM CHECK RE LAY TYPE IJS 278 BUS UNDERVOLTAGE RELAY TYPf HGA14AR 27L LINE UNDERVOLTAGE RELAY TYPF fjGA14AR 52 POWER CIRCUIT BREAKER 52C S CONTROL S ITCH TYPE SB 1 Figure 12 6209561 5 Typical Elementary Diagram of External Connections Type IJS Relays 100 l 90 v i 80 70 I i 0 u 7 t 60 c I __ z I 0 u 50 I 0 _ 1 40 r f 7 I I f __ ll 30 i 20 0 N 7...

Page 15: ...6MM 4 375T 111MM _L__ l I CUTbUT I I I I I 5 687 144MM 112MM j_ 8 81 223M 2 M I 2 18 r 5MM I I PANEL I FOR PANEL DRILLING SEMI FLUSH MOUNTING FRONT VIE 718 1 8MM TYPICAL DIM 3 0 I 76MM 3 4 DRILL 10 HOLES 19MM PANEL DRILLING FOR SURFACE MOUNTING FRONT VIEW 5 16 18 STUD INCHES MM VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS Figure 15 6209271 8 Outline and Panel Drilling Dimensio...

Page 16: ...ST 9 93 200 16 Meter and Control Business Department General Electric Company Protection and Control 205 Great Valley Parkway Malvern Pennsylvania 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 17: ...INSTRUCTIONS GEH 1791 E Supersedes GEH 1791 D SYNCHRONISM CHECK RELAYS TYPES IJS51A AND IJS52A GENERAL fj ELECTRIC w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 19: ...llel with those of the GES or GXS The IJS is not adaptable to applications in volving continuous loading of the contact circuit since contact welding may result even with contact loadings that are low in relation to the interrupting capacity of the contacts The control should be designed to energize the IJS coils when synchronism is to be checked and to permit the IJS contacts to be the last to co...

Page 20: ...it energized varies from 3 seconds on the 20 degree setting to 6 seconds on the 6 0 degree setting at the 10 TDS The Model 12IJS51A3 and 12IJS52A7A relays which are designed for use where the closing angle greater than 20 degrees is required provides 20 seconds delay at the 40 degree closing angle setting as shown in Fig 5 It may be adjusted to other closing angles between 20 and 60 degrees with c...

Page 21: ...Type IJS51A Relay Unit In Cradle Rear View z 9 8 1 w _ 7 Cl Cl z 0 4 u w 3 1 z 2 w 0 0 I 0 I i i 0 0 t t 0 I r I o I l r 0 1 r 0 r r r TTI i I t __j_ ll I I 1 I i I 1 I i i li I i l c u20 CLOSING ANGLE t I I 1 r 1 30 CLOSING ANGLE i lJ I v J I v l _J I I I I I 40 CLOSING ANGLE I i I I I II i I v T I I I H vv l 600 jI I j j J I V CLOSING I ANGLE I I i I I i 50 40 30 20 10 0 10 20 30 40 50 PHASE ANG...

Page 22: ... SHADING_j l t COILS 1 l I l 1 s v i I 6 TOP RfST l l i l8 BOT REST SHORT FINGER it 8 6305ScJ8 3 Intt mal Connections Fo r Type LTS lA Relay Front View V 0 z o VJ I w 20 1 1 c I f I I lb r 1 i 1 I 12 I r t I I I I 4 rr l t t A 1 I I r J I 1 I _____J_ 4 t r _j I I I I I j tT j I 4 6 10 TIME QiAL SUTING Fig 7 6400150 2 Operatine I ime o Type IJS Relay With 2JO Closing Angle Time At 0 115 Volts 60 Cy...

Page 23: ...esired To do this the relay is first disconnected by removing the connection plug which completes the electrical connections between the case blocks and the cradle block To test the relay in its case this connection block can be replaced by a test plug The cover which is attached to the front of the relay case contains an inter lock arm which prevents the cover from being replaced until the connec...

Page 24: ...tion A typical elementary diagram of external con nections is shown in Fig 11 The B contact of 52 in series with only one coil circuit serves to reset the disk and contacts promptly after the circuit breaker closes so that the normal delay is avail able as soon as possible in case the breaker trips again Additional relays undervoltage or reclosing may be considered desirable for prevention of unli...

Page 25: ...C H E C K R E L A Y T Y P E I J I 2 7 8 BUS U N O E RV O L T AGE R E L A Y T Y PF H A14AR 2 7 L L r N E U N OERVO L T A G E R E L A Y r T Y P flGA 4A l 5 2 POW E R C I RC U I T B R E A KE R 5 Z C S CO N T RO L W I TC H T Y P E 58 l Fig 11 6209561 4 Typical Elementary Diagram Of External Connections Type IJS Relays 100 T I 90 1 80 70 u I 60 1 II 1 I 0 u 50 1 I 5 1 4 0 I l 7 1 3 0 1 f7 I I 20 i 10 I...

Page 26: ...en the poles of the U magnet and drag magnet ELECTRICAL ADJUSTMENTS Closing Angle Adjustment Connect the relay as shown in Fig 10 To make an accurate adjustment of the closing angle a phase shifter and phase angle meter are required along with a means for voltage control Two adjustments are necessary for obtaining a desired closing angle The right hand adjustable resistor at the top of the frame p...

Page 27: ...12 223M M 1 5 M M DRI LL El 2 H OLES CUTOUT M AY R EPLACE D R ILLED H OLES O PT I ONAL 2 M M 1 1 6 __ L 7 1 ts Tt tttl t S t3 VIEW SHOWING t8 t A t A ASSEME Y OF HARDwA RE FOR SU RFACE MTG 0 N STEEL PA N EL5 PANEL DRIWNG F SEM J FWSH MOUN TI NG t F RONT VIE W DR I L L 1 0 HOLES 19M M PANEL ORI LUNG FOR 9JRFACE OUNTI NG TF RONT V IE W F i g 14 6 2092 7 1 6 Ou tl i ne And Pa ne l Dr i l l i ng Dimen...

Page 28: ...N ERA L ELECT R I C COMPANY P O W E R SYST E M S M A N A GEMENT BU SINESS DEPT P HILADELPHIA P A 1 91 4 2 G E N E R A L f j E L E C T R I C 5 80 1 0 6 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: