GEH-1768
The 2 ampere tap s hould be us ed with trip coils that take 2 amperes or more at
the minimum control voltage,
provided the tripping current does not exceed 30
amperes at the maximum control voltage.
If the tripping current exceeds 30 amperes ,
an auxiliary relay s hould be used. The auxiliary relay s hould be connected s o that
the tripping current does not pas s through the contacts or the target and s eal-in
coil of the protective relay.
BURDENS
The burdens for the various relay types at rated voltage are s hown in Table 2.
TABLE 2
Tap
115V
230V
460V
Rated
At Rated Voltage
Coil
Coil
Coil
Volt-amps
Power Factor
Watts
IAV54E &
140
280
560
60
3.0
0.26
0.78
IAVSSC
120
240
480
60
4.0
0.26
1.0
105
210
420
60
5.2
0.26
1.4
(Burdens for
93
186
372
60
6.8
0.28
1.9
IAV54F & IAVSSF
82
164
328
60
8.9
0.28
2.5
are approxi-
70
140
280
60
12.4
0.29
3.6
mately 60% of
64
128
256
60
15.1
0.30
4.5
these values )
55
110
220
60
21.6
0.31
6.7
(Burdens for
140
280
560
so
2.5
0.28
0.70
IAV54H & IAVSSH 120
240
480
so
3.3
0.28
0.92
& IAVS4J
are approxi-
105
210
420
so
4.3
0.28
1.2
mately 40% of
93
186
372
so
5.7
0.28
1.6
these values)
82
164
328
so
7.4
0.28
2.1
70
140
280
so
10.3
0.29
3.0
64
128
256
so
12.6
0.30
3.8
55
110
220
so
18.0
0.31
5.6
140
280
560
25
2.3
0.26
0.60
120
240
480
25
3.1
0.26
0.81
105
210
420
25
4.0
0.27
1.1
93
186
372
25
5.2
0.28
1.5
82
164
328
25
6.8
0.28
1.9
70
140
280
25
9.5
0.30
2.8
64
128
256
25
11.6
0.30
3.5
55
110
220
25
16.5
0.31
5.1
RECEIVING, HANDLING AND S TORAGE
These relays , when not included as a part of a control panel, will be s hipped
in cartons designed to protect them agains t damage.
Immediately upon receipt of a
relay, examine it for any damage s us tained in transit.
If damage res ulting from
5