background image

14

4

Open a nearby cold water high demand tap, then open 

the Outlet Valve. This will prevent antifreeze from spreading 

throughout the piping system. Run the tap for 30 minutes. 

Open all other cold water taps in the home and flush 

separately for 1 minute each.

FIGURE 16

Inlet Valve

Bypass Valve

Outlet Valve

5

Close the Inlet Valve and Outlet Valve. Partially drain the 

System using the Manual Flush function for 1 minute to 

depressurize the System. Refer to the Controller Functions 

section under D. OPERATIONS on how to perform a Manual 

Flush sequence. Remove the Plug from the Mini Ball Valve on 

the Inlet Fitting Assembly by depressing the lock ring and 

pulling on the Plug. Slowly open the Mini Ball Valve to ensure 

there is no pressure in the System. Water will flow out, but 

should not spray. Close the Mini Ball Valve immediately. If 

there is spray, repeat the Manual Flush sequence. Replace the 

Plug in the Mini Ball Valve.

FIGURE 17

6

Remove System Cap. If a Stainless Steel Prefilter was 

stored in the Prefilter cavity over the winter remove, wash and 

set aside.

Open

FIGURE 18

7

Be sure the water level in the System is 2” above the 

bottom of the Prefilter cavity. Add more water by slowly 

opening the Inlet Valve if necessary. Add 2 cups (500 ml) of 

unscented household bleach (5 - 6% chlorine) or 1 cup (250 ml) 

chlorine bleach (12% chlorine), maximum 3 months old, to the 

System.

8

Allow the System to soak for 15 minutes. With the 

System Cap tightened, drain the System using the Controller. 

Open the Inlet Valve and allow System to pressurize.

NOTE: If the winterization spring start up is combined with the 
annual maintenance cleaning procedure, the System must 
soak for 60 minutes. If the System is on ground or well water, 
the System must be cleaned with citric acid crystals instead 
of chlorine bleach. Follow the directions on the package for 
preparing the citric acid crystals. Never mix chlorine bleach 
with the citric acid crystals.

9

Open the Outlet Valve and a nearby COLD water tap to 

remove chlorine from the System. Run the tap fully open for 5 

minutes. Further flushing must be performed by the 

homeowner.

10

Close the Inlet Valve and Outlet Valve. Use the Controller 

to depressurize the System. Ensure that there is no pressure 

inside the System as described in Step 5.

11

Open the System Cap and install a new Carbon Prefilter. 

If using a Stainless Steel Prefilter, insert a clean, undamaged 

Stainless Steel Prefilter and replace the System Cap.

Do not remove the Thimble 

Filter from the spigot. If the 

Thimble Filter is dislodged, 

gently push it back down into 

the spigot. If the Thimble Filter 

is damaged, replace with a 

new Thimble Filter.

FIGURE 19

Summary of Contents for Homespring

Page 1: ...1 HomespringTM by GE Water Purifier System Owners Manual...

Page 2: ...CTION 3 B SAFETY WARNINGS 4 5 C CERTIFICATION 5 D OPERATIONS 6 8 E MAINTENANCE SCHEDULE 9 11 F WINTERIZATION 12 15 G TROUBLESHOOTING 15 16 H REPLACEMENT PART LIST AND PROCEDURES 17 21 I SPECIFICATIONS...

Page 3: ...asic principles of household water collection treatment and discharge and some of the features of the Homespring Water Purifier System It is not intended to be a definitive dissertation on the princip...

Page 4: ...rvice provided it is installed commissioned operated maintained and tested in strict accordance to the safety instructions contained in this manual Failure to properly maintain the System will comprom...

Page 5: ...lar to the water pipe 2 Open Inlet and Outlet Valves If ball valves are installed turn the handles in line with the water pipe 3 Plug in the Controller 4 Follow the System Membrane Cleaning section un...

Page 6: ...cial attention under normal operating conditions The System uses existing water pressure in the water supply line to filter water and will continue to operate even during a power failure Electricity i...

Page 7: ...Kit is installed select either Program 3 or Program 4 in this application Water Clarity Advanced Plus Controller Low Turbidity Less than 0 5 NTU Program 1 Medium Turbidity Peaks to 1 0 NTU less than 7...

Page 8: ...utton is held down for 5 seconds the Drain Solenoid Valve will remain open for 5 minutes To interrupt flushing press MANUAL FLUSH again The Drain Solenoid Valve will be closed automatically after 5 mi...

Page 9: ...be performed every 12 months unless specified otherwise Refer to H REPLACEMENT PART LIST AND PROCEDURES for part numbers System Part Annual Maintenance Tasks UFC 211 UF 211 Carbon Prefilter Replace W...

Page 10: ...tire procedure to avoid contaminated water entering the household distribution system Contaminated water might cause personal injury and in some cases death This cleaning procedure does NOT disinfect...

Page 11: ...ath Replace the System Cap Vertical Systems or the Brass Plug Horizontally mounted Systems Let stand for 60 minutes Annual Maintenance Check Summary The Homespring Authorized Technician performs the f...

Page 12: ...etely drain the System and household piping To drain the System refer to the Controller Functions section under D OPERATIONS on how to perform a Manual Flush To drain the household pipes open a cold w...

Page 13: ...vity FIGURE 13 7 If a Stainless Steel Prefilter has been set aside place the Stainless Steel Prefilter in the Prefilter cavity 8 For all Sytems replace the System Cap using the Cap Wrench and check bo...

Page 14: ...ssary Add 2 cups 500 ml of unscented household bleach 5 6 chlorine or 1 cup 250 ml chlorine bleach 12 chlorine maximum 3 months old to the System 8 Allow the System to soak for 15 minutes With the Sys...

Page 15: ...ace is clean and is intact Ensure connections are tight Contact your Dealer System water flow is noticeably reduced Check if Thimble Filter is clogged Depressurize System remove System Cap and Interna...

Page 16: ...unctions section under D OPERATIONS on how to perform a manual flush sequence and ensure button on controller is pressed for a full 5 seconds A buzz sound should be heard from the Drain Solenoid Valve...

Page 17: ...remove the System Cap 4 Put on a pair of disposable gloves and carefully remove and dispose of the Internal Prefilter Check that the Thimble Filter is in place seated in the spigot DO NOT attempt to...

Page 18: ...18 UFC 211 and UF 211 Series FIGURE 20 24 13 6 10 3 5 11 1 2 17 18 20 19 21 16 4 3 7 8 22 23 14 15 12 9...

Page 19: ...3024987 Cap Wrench UF 211 X 14 Backpulse Tank X 15 3035560 Controller Power Supply DC X Sub Assembly Kits 16 3025172 Installation Sub Assembly Kit Base shims anchors Mini Ball Valves with Plugs 2 Nylo...

Page 20: ...4 FNPT Flapper X 6 3025096 Brass Nipple 3 4 X 7 3030405 External Prefilter Housing and Head X 8 3025174 Wall Bracket Kit Filter Housing X 9 3025371 Mini Ball Valve Plug 1 4 X 10 3024982 Mini Ball Val...

Page 21: ...aims are based on a continuous flow of 4 5 gpm 17 Lpm 2 Pressure drops are given for systems when they are new and equipped as specified by the model number At temperatures below 77 F 25 C the pressur...

Page 22: ...nside the dwelling will be significantly reduced during System cleaning Flushing Flushing includes a Front flush and a Back flush Systems that are installed in municipal cistern or ground water source...

Page 23: ...een a water quality issue such as a recent boil water alert or water main break from the municipal water source the household pipes should be sanitized upon installation of the System How long does th...

Page 24: ...ling the System excluding the attached parts will need to be replaced Will the System remove iron sulfur The pore size of the membrane is 0 02 microns nominal which may help in the filtration of parti...

Reviews: