background image

10

Close the Inlet and Outlet Valves. Using the Controller, 

initiate a Manual Flush sequence to bring System pressure 

close to zero. Refer to the instructions in the Controller 

Functions section under D. OPERATIONS on how to perform a 

Manual Flush sequence. Slowly open the Mini Ball Valve to 

ensure there is no pressure in the System. Water will flow out, 

but should not spray. Close the Mini Ball Valve immediately. If 

there is spray, repeat the Manual Flush sequence. Reinsert the 

Plug into the Mini Ball Valve.

3

Vertical Systems:

Remove the System Cap using the Cap Wrench. The water 

level should be at least 2” above the Internal Prefilter spigot.
If the water level is below 2”, open the Inlet Valve slowly to 

raise the water level. 

FIGURE 7 

Once the cap is removed, wipe the System Cap out with a 

clean, soft cloth, remove the O-ring carefully, wipe the O-ring 

with a clean cloth, check the O-ring for damage or wear, apply 

a very small amount of DOW CORNING 111 silicone lubricant 

on the O-ring, and replace the O-ring. If necessary, replace the 

O-ring with a new O-ring. 

Horizontally-mounted Systems: 

Ensure that there is still some water inside the System after 

the Manual Flush. Do not empty the System completely. If 

water stops coming out during the Manual Flush, open the 

Inlet Valve slowly to fill the System again. 

  

WARNING: 

Do not use a bottle of 

bleach more than 3 months old.
If a Bypass Valve is installed, the Bypass Valve 

should be closed for the entire procedure to avoid 

contaminated water entering the household 

distribution system. Contaminated water might cause 

personal injury and in some cases death.
This cleaning procedure does NOT disinfect the 

household pipes. If potentially microbiologically 

unsafe water is present in the pipes, it is strongly 

recommended that all pipes be sanitized.

For Ground Water Systems, refer to Ground Water 

Application Cleaning Procedures section before beginning 

this step.
Vertical Systems:

With the Internal Prefilter still removed, pour 2 cups 

 

(500 ml) of 5 - 6% unscented household chlorine bleach 

OR 1 cup (250 ml) of 12% chlorine bleach into the Prefilter 

cavity. Replace the System Cap. Slowly open the Inlet Valve to 

pressurize the System. Let stand for 60 minutes.

Horizontally-mounted Systems:

With the Internal Prefilter still removed, unscrew the 

½

” 

Brass 

Plug on the Air Vent Assembly near the System Cap.

FIGURE 8 

Brass Plug

Pour 2 cups (500 ml) of 5 - 6% unscented household chlorine 

bleach OR 1 cup (250 ml) of 12% chlorine bleach into the 

System Casing cavity. A funnel may be used in this step to 

assist pouring. Replace the ½” Brass Plug. Slowly open the 

Inlet Valve to pressurize the System. Let stand for 60 minutes.

Using the Controller, activate the Manual Flush 

sequence. Refer to the instructions in the Controller Functions 

section under D. OPERATIONS on how to perform a Manual 

Flush sequence. Once the flushing is complete, open the Outlet 

Valve and a nearby COLD water tap to flush most of the 

chlorine from the System. Run the tap fully open for at least 60 

minutes.

NOTE: Use only COLD water taps and continue the flow of 
water until there is no chlorine smell.

Summary of Contents for Homespring

Page 1: ...1 HomespringTM by GE Water Purifier System Owners Manual...

Page 2: ...CTION 3 B SAFETY WARNINGS 4 5 C CERTIFICATION 5 D OPERATIONS 6 8 E MAINTENANCE SCHEDULE 9 11 F WINTERIZATION 12 15 G TROUBLESHOOTING 15 16 H REPLACEMENT PART LIST AND PROCEDURES 17 21 I SPECIFICATIONS...

Page 3: ...asic principles of household water collection treatment and discharge and some of the features of the Homespring Water Purifier System It is not intended to be a definitive dissertation on the princip...

Page 4: ...rvice provided it is installed commissioned operated maintained and tested in strict accordance to the safety instructions contained in this manual Failure to properly maintain the System will comprom...

Page 5: ...lar to the water pipe 2 Open Inlet and Outlet Valves If ball valves are installed turn the handles in line with the water pipe 3 Plug in the Controller 4 Follow the System Membrane Cleaning section un...

Page 6: ...cial attention under normal operating conditions The System uses existing water pressure in the water supply line to filter water and will continue to operate even during a power failure Electricity i...

Page 7: ...Kit is installed select either Program 3 or Program 4 in this application Water Clarity Advanced Plus Controller Low Turbidity Less than 0 5 NTU Program 1 Medium Turbidity Peaks to 1 0 NTU less than 7...

Page 8: ...utton is held down for 5 seconds the Drain Solenoid Valve will remain open for 5 minutes To interrupt flushing press MANUAL FLUSH again The Drain Solenoid Valve will be closed automatically after 5 mi...

Page 9: ...be performed every 12 months unless specified otherwise Refer to H REPLACEMENT PART LIST AND PROCEDURES for part numbers System Part Annual Maintenance Tasks UFC 211 UF 211 Carbon Prefilter Replace W...

Page 10: ...tire procedure to avoid contaminated water entering the household distribution system Contaminated water might cause personal injury and in some cases death This cleaning procedure does NOT disinfect...

Page 11: ...ath Replace the System Cap Vertical Systems or the Brass Plug Horizontally mounted Systems Let stand for 60 minutes Annual Maintenance Check Summary The Homespring Authorized Technician performs the f...

Page 12: ...etely drain the System and household piping To drain the System refer to the Controller Functions section under D OPERATIONS on how to perform a Manual Flush To drain the household pipes open a cold w...

Page 13: ...vity FIGURE 13 7 If a Stainless Steel Prefilter has been set aside place the Stainless Steel Prefilter in the Prefilter cavity 8 For all Sytems replace the System Cap using the Cap Wrench and check bo...

Page 14: ...ssary Add 2 cups 500 ml of unscented household bleach 5 6 chlorine or 1 cup 250 ml chlorine bleach 12 chlorine maximum 3 months old to the System 8 Allow the System to soak for 15 minutes With the Sys...

Page 15: ...ace is clean and is intact Ensure connections are tight Contact your Dealer System water flow is noticeably reduced Check if Thimble Filter is clogged Depressurize System remove System Cap and Interna...

Page 16: ...unctions section under D OPERATIONS on how to perform a manual flush sequence and ensure button on controller is pressed for a full 5 seconds A buzz sound should be heard from the Drain Solenoid Valve...

Page 17: ...remove the System Cap 4 Put on a pair of disposable gloves and carefully remove and dispose of the Internal Prefilter Check that the Thimble Filter is in place seated in the spigot DO NOT attempt to...

Page 18: ...18 UFC 211 and UF 211 Series FIGURE 20 24 13 6 10 3 5 11 1 2 17 18 20 19 21 16 4 3 7 8 22 23 14 15 12 9...

Page 19: ...3024987 Cap Wrench UF 211 X 14 Backpulse Tank X 15 3035560 Controller Power Supply DC X Sub Assembly Kits 16 3025172 Installation Sub Assembly Kit Base shims anchors Mini Ball Valves with Plugs 2 Nylo...

Page 20: ...4 FNPT Flapper X 6 3025096 Brass Nipple 3 4 X 7 3030405 External Prefilter Housing and Head X 8 3025174 Wall Bracket Kit Filter Housing X 9 3025371 Mini Ball Valve Plug 1 4 X 10 3024982 Mini Ball Val...

Page 21: ...aims are based on a continuous flow of 4 5 gpm 17 Lpm 2 Pressure drops are given for systems when they are new and equipped as specified by the model number At temperatures below 77 F 25 C the pressur...

Page 22: ...nside the dwelling will be significantly reduced during System cleaning Flushing Flushing includes a Front flush and a Back flush Systems that are installed in municipal cistern or ground water source...

Page 23: ...een a water quality issue such as a recent boil water alert or water main break from the municipal water source the household pipes should be sanitized upon installation of the System How long does th...

Page 24: ...ling the System excluding the attached parts will need to be replaced Will the System remove iron sulfur The pore size of the membrane is 0 02 microns nominal which may help in the filtration of parti...

Reviews: