31
Installing the Controller
WARNING:
To ensure personal safety
and that the internal fuse in the 24 VDC transformer
is not blown during installation, install the plug from
the transformer into the controller terminals labeled
24 VDC before plugging the transformer into an outlet.
Failure to do so may result in the leads touching
together and shorting out the transformer resulting in
irreparable damage to the transformer.
1
Use the provided plastic anchor if necessary. Ensure that
the controller is within the proximity of the system so that the
cables can reach the drain solenoid valve and the inlet
solenoid valve (for systems equipped with the surface water
option kit only).
Drill a hole suitable for a #8 screw on an adjacent wall. Insert a
#8 screw in this hole and tighten the screw, leaving a 1/4" gap
between the screw head and the wall. Drill a hole suitable for
a #8 screw on an adjacent wall. Insert a #8 screw in this hole
and tighten the screw, leaving a 1/4" gap between the screw
head and the wall.
The transformer cable should also be long enough to reach the
electrical receptacle. Do not connect any cables at this time.
Not-To-Scale
Transformer
Drain Solenoid
Valve
Inlet Solenoid
Valve
Controller
figure 54
2
Mount the controller using the keyhole located at the
back of the controller on the screw head. Level the controller.
Remove the controller front cover and drill two additional
holes suitable for a #8 screw into these two holes and secure
the controller to the wall by tightening the two screws. Use the
plastic anchors if necessary.
24 VDC from
Transformer
To Drain
Solenoid Valve
To Inlet
Solenoid Valve
Advanced
Plus Controller
figure 55
3
Ensure the transformer is not plugged into the electrical
receptacle. Connect the power supply cable from the
transformer to the 24 VAC terminals on the controller. Polarity
is not important.
4
Connect the drain solenoid valve cable to the “drain”
terminals on the controller. Refer to Figure 55.
5
Applicable to Systems Equipped with the Surface
Water Option Kit Only:
Connect the inlet solenoid valve cable to the “inlet” terminals
on the controller. Refer to Figure 55. Polarity is not important.
6
Install the two AA batteries (provided) in the controller.
Replace the controller front cover and plug the transformer
into the electrical receptacle.
WARNING:
Use only the supplied
electrical transformer. Failure to follow this instruction
will void the warranty.