CHAPTER 10: PROGRAMMING GROUP 1
60
EPM 5000 series Advanced Power Meters
GE Multilin
SECONDARY PT VALUES
PT RATIO
FULL SCALE
75 V (Suffix 75) L-N MAX
120:1
9.00 KV
120/208 V
1:1 (Direct)
120.0
120/208 V
4:1
0480 V
120/208 V
120:1
014.4 KV
277/480 V (Suffix G)
1:1 (Direct)
0300 V
120/208V 600:1
072.0
KV
120/208 1150:1
138.0
KV
Table 10-2
: TYPICAL Full Scale Settings for Volts
If PT is connected line to line, the full scale can be 14.40 KV. Full scale is
300
V L-N, not 277, because
the factory calibration is 300 V. Be sure the table is based on a meter regulation of 2000 A/D counts.
Thus, for best accuracy, all settings should be placed within that range.
VOLTAGE FULL SCALE:
To change the Full Scale Settings:
NOTE
: Press
MAX/MIN/LIMITS
at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a.
Enter Group Level of Programming Mode
(see Chp. 8).
b.
Press
MAX/MIN/LIMITS
until
1.
appears in upper
display.
Step 2:
a.
Press
AMPS
to activate GROUP 1.
!
10.
appears in upper display.
!
Middle display indicates Scale Factor Setting.
!
Lower display indicates Full Scale for voltage.
Summary of Contents for EPM 5200
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin ...