CHAPTER 16: ETHERNET OPTION
GE Multilin
EPM 5000 series Advanced Power Meters
95
16.7: Configuration Parameters
After entering Setup Mode (confirm by pressing Enter), you an configure the parameters by entering one
of the numbers on the Change Setup Menu, or you can confirm default values by pressing
Enter
. Be
sure to store new configurations when you are finished. The Ethernet Interface will then perform a power
reset.
Serial Number 5415404 MAC Address 00:20:4A:54:3C:2C
Software Version V01.2 (000719)
Press Enter to go into Setup Mode
1) Network/IP
Settings:
Ethernet Interface Autodetect
IP Address
- 0.0.0.0/DHCP (Customer Configurable)
Default Gateway
--- not set --- (Customer Configurable)
Netmask
--- not set --- (Customer Configurable)
2) Serial & Mode Settings:
Protocol
Modbus/RTU, Slave(s) attached (FIXED)
Serial
Interface
9600,8,N,1,RS232,DB25 (must match meter) (FIXED)
3) Modem
Control
Settings:
DCD
Output
Fixed
High/Active
CTS Output
Fixed High Active
4) Advanced Modbus Protocol Settings:
Slave Addr/Unit Id Source
Modbus/TCP header (FIXED)
Modbus Serial Broadcasts
Disabled
Character, Message Timeout 00010 ms, 00500 ms
D) default settings, S) save, Q) quit without save;
select command or parameter set (1..4) to change:
I
BAUD RATE
The Ethernet Interface and attached serial device (the meter) must agree on a speed or baud rate used
for the serial connection. Valid baud rates are 1200, 2400, 4800 and 9600 (default). For the EPM 5350P,
default settings are
9600 baud rate, 8 data, 1 stop, no parity, Modbus RTU
.
Summary of Contents for EPM 5200
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin ...