CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
GE Multilin
EPM 5000 series Advanced Power Meters
55
9.9: Group 0, Function 6—KYZ Parameter Selection
NOTE
: FUNCTION 6 applies only if Option -NL or -NL2 was ordered.
OPTION -NL
: This option gives the meter 2 Relays and one KYZ pulse. The KYZ pulse can be
programmed to the below features.
Select a single parameter from
Table 9-5
according to the EPM 5300P model being programmed.
OPTION -NL2
: This option offers 3 distinct KYZ pulses instead of Relays.
Only three separate parameters may be selected: FUNCTION 6.0 (KYZ Port 0), FUNCTION 6.1 (KYZ
Port 1), and FUNCTION 6.2 (KYZ Port 2). The available parameters vary according to the EPM 5300P
model being programmed. For exact port positions see Installation Sections.
PARAMETER DESCRIPTION
0 Disable
KYZ
1
Positive Watt Hour KYZ
2
VA Hour KYZ
3
Negative Watt Hour KYZ
4
Positive VAR Hour KYZ
5
Negative VAR Hour KYZ
Table 9-5
: KYZ Parameters
APPLICABLE SELECTIONS
: 5300P - +WH, -WH, VAH
5300P+R* - +WH, -WH, +VARH, -VARH
* (-R option gives the 5300P VAR/Hour readings instead or VA/Hours).
To perform the KYZ Parameter Selection:
NOTE
: Press
MAX/MIN/LIMITS
at any time to cancel before storing the last digit or switch.
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
MAX/MIN
LIMITS
KVAR
PF
KW
KVA
FREQ
KWH
KVAH
AC VOLTS
AC AMPS
POWER
N
C
B
A
MAX
MIN
A
N
B
N
C
N
A
B
B
C
C
A
LM2
LM1
NEXT
PHASE
VOLTS AMPS
POWER
Step 1:
a.
Enter Group Level of Programming Mode
(see Chp. 8).
b.
Press
MAX/MIN/LIMITS
until
0.
appears in
upper display.
c.
Press
AMPS
to activate the Group.
Step 2:
a.
Press
MAX/MIN/LIMITS
until
06.P
appears in
upper display.
(Standard Selection is 1).
Summary of Contents for EPM 5200
Page 2: ......
Page 30: ...CHAPTER 4 COMMUNICATION INSTALLATION 26 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 70: ...CHAPTER 10 PROGRAMMING GROUP 1 66 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 88: ...CHAPTER 14 EXITING PROGRAMMING MODE 84 EPM 5000 series Advanced Power Meters GE Multilin ...
Page 94: ...CHAPTER 15 PROGRAMMING QUICK REFERENCE 90 EPM 5000 series Advanced Power Meters GE Multilin ...