GENER
AL
PR
ODUCT
OPER
A
TION
SCREEN MODE
CURVES
REGISTER
INST
ALL
A
TION
C
ONNECTION
EntelliGuard G
INTRO
TRIP UNIT
APPENDIX
2-26
E
D
PT CONN
PH-PH
PH-PH
...save chosen value
PH-N
PT VOLTAGE
120
120
...save chosen value
600
ALARM1
ON
PICKUP
0,5
0,5
0,55
1
...save chosen value
ALARM1
OFF
PICKUP
0,5
0,5
0,55
1
...save chosen value
ALARM2
ON
PICKUP
0,5
0,5
0,55
1
...save chosen value
NEUTRAL
100%
50%
63%
100
...save chosen value
PWR DMD
INTERVAL
5
5
6
60
...save chosen value
WAVEFORM
CAPTURE
--
DISABLE
...save chosen value
ALL
POWER
DIRECTION
FREQUENCY
50 cycles
50Hz
...save chosen value
60Hz
E
MODBUS
BAUDRATE
19200
19200
...save chosen value
300
MODBUS
ADDRESS
1
0
...save chosen value
254
PASSWORD
0
Back to SETUP
LANGUAGE
ENGLISH
ENGLISH
...save chosen value
FRANCAIS
SET DATE
Y 0
M 0
D 0
SET DATE
Y 0
M 0
D 0
0
...save chosen value
...
0
...save chosen value
...
SET TIME
H 0
M 0
S 0
POWER
REVERSAL
1
2
15
...save chosen value
PICKUP:
10kW
DELAY (sec):
1
RELAY 1
GROUP 1
GROUP 1
...save chosen value
GROUP 1
INPUT 1
OFF
OFF
...save chosen value
RELT
TRIP
RELAY 2
GROUP 1
GROUP 1
...save chosen value
GROUP 1
RELT
OFF
OFF
...save chosen value
REMOTE
ON
INPUT 2
OFF
OFF
TRIP
...save chosen value
CURRENT
UNBAL
PICKUP
10%
DELAY (sec): 1
10
11
50
...save chosen value
C
CURRENT
UNBAL
POWER
REVERSAL
PICKUP:
10kW
DELAY (sec): 1
10
20
990
...save chosen value
PICKUP
10%
DELAY (sec): 1
OFF
1
15
...save chosen value
D