DigitalFlow™ XGS868i Programming Manual
125
Appendix C. Programming the XGS868i Using PanaView™
C.6.3 Entering Communications Data
The Model XGS868i flowmeter is equipped with an RS232 or an RS485 serial interface. An RS485 option is also
available with MODBUS capability. When the MODBUS option is present, the XGS868i may also have the standard
RS232 serial interface.
The serial port is used to transmit stored data and displayed readings to a personal computer by connecting the meter’s
serial interface to the serial port of the PC. In addition, the Model XGS868i can receive and execute remote commands,
using
PanaView
software, via this link.
Use the
Comm
port
submenu to set the communications port and MODBUS parameters. While following the
programming instructions, refer to Figure 54 on page 141 of Appendix D,
PanaView Menu Maps
.
Note:
For a more detailed explanation of the MODBUS interface, refer to Chapter 1,
Setting Up MODBUS
Communication
C.6.3a Setting Up the Serial Port
1.
To enter this submenu from the
Global
menu, highlight and double-click on the
Comm port
option in the center
pane.
2.
Enter a
Meter Address
number between 1 and 254 and click
[Next Item].
The default number is 1.
A meter address is only necessary for communication with the GE Measurement & Control
PanaView
software. See
the
PanaView User’s Manual
for more information.
IMPORTANT:
If the meter address or baud rate is changed, communication with PanaView must be re-established with
the new address number.
3.
Double-click on the desired
Baud Rate
(from 300 to 19,200).
If you have the RS485 MODBUS option, proceed to step 4 below. If you have the standard RS232 serial interface, the
meter exits the
Comm port
submenu and returns to the
Global PROGRAM
prompt.
Note:
The XGS868i MODBUS communication settings chosen in the next four steps must match those of the
MODBUS control system.
4.
Double-click on the desired
MODBUS Baud Rate
(from 2400 to 19,200).
5.
Double-click on the desired
MODBUS Parity
(None, Odd or Even).
6.
Double-click on the desired
MODBUS Stop Bits
(1 or 2).
7.
Enter the desired
MODBUS Address.
The meter exits the
Comm port
submenu and returns to the
Global
window. Click
[Exit Page]
once to return to the
Site
Edit Menu
, and
[Close]
to exit the
Site Edit Menu
.
IMPORTANT:
You must reboot the XGS868i to load the new settings.
Refer to the section
Requesting Parameters Using MODBUS
on the following page to retrieve data from the XGS868i
using MODBUS.
Summary of Contents for DigitalFlow XGS868i
Page 2: ......
Page 4: ... no content intended for this page ...
Page 10: ...Contents viii DigitalFlow XGS868i Programming Manual ...
Page 52: ...Chapter 1 Programming Site Data 42 DigitalFlow XGS868i Programming Manual ...
Page 85: ...DigitalFlow XGS868i Programming Manual 75 Appendix A Menu Maps Appendix A Menu Maps ...
Page 86: ...76 DigitalFlow XGS868i Programming Manual no content intended for this page ...
Page 96: ...86 DigitalFlow XGS868i Programming Manual no content intended for this page ...
Page 146: ...Appendix C Programming the XGS868i Using PanaView 136 DigitalFlow XGS868i Programming Manual ...
Page 148: ...138 DigitalFlow XGS868i Programming Manual no content intended for this page ...
Page 174: ...Warranty 164 DigitalFlow XGS868i Programming Manual no content intended for this page ...
Page 175: ......