OPM_LPE_11X_3K0_10K_1GB_V041
34
GE DE LP 11 UPS: User manual 4.1 (GB)
UPS Type
:
LP 3-11
LP 5-11
LP 6-11
LP 8-11
LP 10-11
AUTOMATIC BYPASS SWITCH
The automatic switch provides transfer of the load to the mains voltage without any interruption of the supply. The transfer is
initiated by a signal from the output converter protection circuit in case of an overload or high temperature.
When the conditions return to normal the load is automatically transferred back to the output converter. The automatic
bypass switch can be disabled by the end-user.
Bypass voltage limits
:
±10% of nominal
Transfer transients
:
typically 2% mean deviation over one half cycle.
Frequency tracking range
:
± 2/4/6% of nominal (user selectable)
Slew rate
:
max. 1Hz/sec or 5Hz/sec (user selectable)
BATTERY
Battery type
:
Sealed and maintenance free
Nominal voltage (V) / capacity (Ah)
:
12/7 12/7 12/7 12/12
12/12
Number
of
batteries
:
12 20 20 20 20
Capacity of standard battery set
:
7 Ah
7Ah
7Ah
12Ah
12Ah
Battery recharge time
:
1.5 - 3 hours for 80% capacity
Battery service life
:
up to 6 years (depending on operating conditions)
Battery discharging
:
self discharge current 0.35 mA
discharge end voltage of the battery depending on the actual load
10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA
When the LP-11 is in sleeping mode the inverter will be switched off, battery
charger and rectifier are in operation
Runtime in minutes
VA / Watts
1000 / 800
:
30
60
60
120
120
2000 / 1600
:
15
40
40
60
60
3000 / 2400
:
10
18
18
40
40
5000 / 4000
:
-
10
10
22
22
6000 / 4800
:
-
-
8
17
17
8000 / 6400
:
-
-
-
11
11
10000
/
8000
:
- - - - 8
BATTERY EXTENSION PACKS
Sheet steel cubicle
:
VSDA1
Dimensions (hxwxd, mm)
:
537x313x590
Battery
:
240Vdc/7Ah or 240Vdc/14Ah
Weight with battery
:
70kg or 120kg (without batt: 20kg)
Battery pack A (voltage V / capacity Ah)
:
n.a.
240/7 240/7 240/7 240/7
Total
capacity
(Ah)
:
n.a.
14 14 19 19
Typical runtime, 100% / 50% load, min. :
n.a.
25/60
21/50 22/50 16/39
Number of packs required
:
n.a.
1
1
1
1
Extension B (voltage V / capacity Ah) :
n.a.
240/14 240/14 240/14 240/14
Total
capacity
(Ah)
:
n.a.
21 21 26 26
Typical runtime, 100% / 50% load, min. :
n.a.
45/90
35/75 33/70 25/57
Number of packs required
:
n.a.
1
1
1
1
For more info see section 7.1
ENCLOSURE
Sheet steel cubicle
:
VSD1
VSD1
VSD1
VSD2
VSD2
Colour front
:
aluminum
Colour cabinet
:
RAL 9010 (white)
Protection :
IP
20
Dimensions (hxwxd, mm)
:
537x313x590 537x313x590 537x313x590 680x313x720 680x313x720
(height with castors)
Weight
(with
batteries)
:
85kg 110kg 115kg 165kg 170kg
GENERAL DESIGN CRITERIA
Mechanical :
IP20
Humidity
:
95% non condensing
Safety
:
EN 50091-1; EN 60950; IEC 950
EMC
:
EN 50091-2
Surge capability
:
IEC 1000-4-5 (6kV 1.2/50µs, 3kA 8/20µs)