3.4 Automatic Bypass Switch
If the output converter is unable to deliver the demanded output power because of overload or overtemperature,
the automatic bypass switch will automatically transfer the load to the utility. When the situation is corrected the
UPS will switch back to normal operation, i.e. the load is transferred back to the output converter. Though the
automatic bypass switch is shown as a simple mechanical switch in figures 2-5, the transfers are done by
means of thyristors, i.e. electronically, without any interruption of the power supplied to the load.
In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to
protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the
software in order to protect the UPS and connected equipment.
TO LOAD
AUTOMATIC
BYPASS
SWITCH
FRONT
PANEL
1-PHASE
MAINS INPUT
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 4. Bypass operation: automatic bypass
If a power failure occurs during bypass operation, load power is lost. If the UPS functions under overload
conditions it may not be able to protect the load.
3.5 Manual Bypass Switch (Service switch)
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-
position switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly
connected to the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is
possible without interruption of the power supplied to the load.
CAUTION:
REFER SERVICE TO QUALIFIED PERSONNEL ONLY
.
TO LOAD
STANDARD
INSTALLED:
RS232/
CONTACT
INTERFACE
OPTION
SLOTS FOR:
RPA CARD
SNMP CARD
RELAY CARD
RFI
FILTER
AUTOMATIC
BYPASS
SWITCH
FRONT
PANEL
1-PHASE
MAINS INPUT
MANUAL BYPASS SWITCH
OUTPUT
CONVERTER
SYSTEM
ON/OFF
MICROPROCESSOR CONTROL
BATTERY
EXTENSION
OPTIONAL
RFI
FILTER
INPUT
CONVERTER/
BATTERY
CHARGER
BYPASS
FILTER
Figure 5. Bypass operation: manual bypass
OPM_LPE_11X_3K0_10K_1GB_V041
7
GE DE LP 11 UPS: User manual 4.1 (GB)