![background image](http://html1.mh-extra.com/html/ge/diac/diac_manual_4129709046.webp)
*(.%
45
SPECIFICATIONS
Ratings
Frequency
50 / 60 Hz
Current
1A or 5A Models
Maximum Permissible Current
1A Model / 5A Model
Continuous 3 A
15 A
3 Second 50 A
250 A
1 Second 100 A
500 A
Operating Current Range
1A Model / 5A Model
minimum .095 A .475 A
I
2
T
(constant) 1520
38000
Maximum Transient Overreach 7%
Burdens
AC Current Circuit:
1A / 5A Unit Burden
0.1 / 0.5A
0.45VA
1.0 / 5A
2.6VA
See Figure 30 for curve and Table 3.
Contact Ratings
Output Contacts
Voltage
Cont.
Make
&
carry
1 sec.
Break
Max
load
DC
Resistive
125V
250V
10A
30A
.5A
.3A
60W
DC
Inductive
L/R=40ms
125V
250V
370V
10A
30A
.25A
.15A
.05A
50VA
NOTE: Suitable for Cap-Trip devices.
Environmental
Ambient Temperature:
Storage:
-40 to +85
o
C
Operation: -40 to +70
o
C
Humidity:
Up to 95%
without condensing.
Insulation Withstand Tests:
Impulse Voltage:
5KVpeak,1.2/50
m
s,
0.5 Joules.
Per: IEC255-5, Class III
Surge Withstand Capability:
Fast Transient:
Per: ANSI C37.90.1
Per: IEC 255-22-4
Class IV
Oscillatory:
Per: ANSI C37.90.1
Per: IEC 255-22-1,
Class IV
Radio Frequency Withstand:
25MHZ-1GHZ
Keyed every 1MHZ
for 2 seconds.
Per: ANSI C37.90.2
Per: IEC 255-22-3
Electrostatic Discharge:
Per: IEC 225-22-2
Summary of Contents for DIAC
Page 29: ...28 FIGURE 18 DIAC and DSFC External Internal Connections...
Page 30: ...29 FIGURE 19 DIFC External Internal Connections...
Page 31: ...30 FIGURE 20 DIAC Panel Mounting and Drilling...
Page 32: ...31 FIGURE 21 DIFC Panel Mounting and Drilling...
Page 33: ...32 FIGURE 21A SURFACE MOUNTING DIFC...
Page 34: ...33 FIGURE 22 DSFC Panel Mounting and Drilling...
Page 42: ...41 FIGURE 27 9819647 8919648 DIAC Front and Rear Views...
Page 43: ...42 FIGURE 28 8919652 8919653 DIFC Front and Rear Views...
Page 44: ...43 FIGURE 29 8919632 8919661 DSFC Front and Rear Views...