7. ACCEPTANCE TESTS
GEK-98514B
BUS1000 Busbar Protection
7-3
7.6.1.1. Main Unit
Set the following adjustments in the differential boards:
-Slope: 0,5 (bridge on the left side of the board)
-Supervision: 0,2 (bridge on the right side of the board)
Apply current through terminals 23 and 26 of the position for phase 1, through 24 and 26 for phase 2,
through 25 and 26 for phase 3 and check that in all 3 instances, the corresponding main units operate
according to the following table:
SLOPE
PICKUP CURRENT
0.5
0.190 - 0.210
0.6
0.237 - 0.263
0.7
0.313 - 0.347
0.8
0.475 - 0.525
Also check that contact 1, 2 of the position closes. (if the alarm operates, the contact will open)
Each time the differential unit operates the following contacts will close: X29-X30, X31-X32. These contacts
will remain closed until the reset button (place in cabinet 1 front panel) is pushed.
NOTE
: Should the alarm go off as a result from the current having been applied for over 10 s, the differential
will be blocked and the corresponding red light in the test box will light up, and a message will show
up on the alarm’s screen. In such event, to proceed with the test, the differential should be reset by
pressing the corresponding green button, and acknowledge the alarm to clear up the screen of the
alarms.
7.6.1.2. Supervision Units
Set the following adjustments in the differential boards:
-Slope: 0,5 (bridge on the left side of the board)
-Supervision: 0,2 (bridge on the right side of the board)
Apply current through terminals 23 and 26 of the position for phase 1, through 24 and 26 for phase 2,
through 25 and 26 for phase 3 and check that in all 3 instances, the corresponding supervision units operate
according to the following table:
ADJUSTM. VALUE
PICKUP VALUE
0.2
0.190-0.210
0.3
0.285-0.315
0.5
0.475-0.525
0.8
0.760-0.840
1.0
0.950-1.050
1.5
1.425-1.575
2
1.900-2.100
Also check that contact 1, 2 of the position closes. (if the alarm operates, the contact will open)
Each time the differential unit operates the following contacts will close: X29-X30, X31-X32. These contacts
will remain closed until the reset bottom (place in cabinet 1 front panel) is pushed.
Summary of Contents for BUS1000
Page 6: ......
Page 8: ......
Page 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Page 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Page 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Page 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Page 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Page 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Page 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...