5. HARDWARE DESCRIPTION
5-8
BUS1000 Busbar Protection
GEK-98514B
5.3.6. INTERNAL ADJUSTMENTS
Percent slope adjustment (FIG. 12)
It is placed in the differential board (DDF) and it is achieved by means of a Cambion jumper. The range
values are: 0.5, 0.6, 0.7, and 0.8
Differential overcurrent supervision adjustment (FIG. 12)
It is placed in the differential board (DDF) and it is achieved by means of a Cambion jumper. The range
values are: 0.2, 0.3, 0.5, 0.8, 1.0, 1.5 and 2.
Alarm operation time adjustment (FIG. 13)
It is placed in the alarm board (DAL) and it is achieved by means of the P1 potentiometer. It is adjusted at 10
s.
Failure pickup command seal in adjustment (fig. 14)
It is placed in the breaker failure board (SFI) and it is done by means of a jumper.
5.3.7. FACTORY ADJUSTMENTS
DDF board (FIG. 12)
•
P1 potentiometer: Differential unit operation level adjustment.
•
P2 potentiometer: Differential unit operation time adjustment.
•
P3 potentiometer: Differential unit recovering time adjustment.
•
P4 potentiometer: Supervision unit operation level adjustment.
•
P5 potentiometer: Supervision unit operation time adjustment.
•
P6 potentiometer: Supervision unit fill-in time adjustment
DAL board (FIG. 13)
P1 potentiometer: Alarm unit recovering time adjustment.
SFI board (FIG. 14)
•
P1 potentiometer: Breaker failure operation level adjustment.
•
P2 potentiometer: Overcurrent unit operation level adjustment.
•
P3 potentiometer: Overcurrent unit fill-in time adjustment.
•
P4 potentiometer: Breaker failure unit fill-in time adjustment.
•
P5 potentiometer: Overcurrent unit operation time adjustment
NOTE
: The potentiometers described above are factory adjusted and it is not recommended to change their
original adjustment positions.
Summary of Contents for BUS1000
Page 6: ......
Page 8: ......
Page 34: ...5 HARDWARE DESCRIPTION 5 10 BUS1000 Busbar Protection GEK 98514B ...
Page 36: ...6 RECEIVING HANDLING AND STORAGE 6 2 BUS1000 Busbar Protection GEK 98514B ...
Page 54: ...8 FINAL INSTALLATION AND COMMISSIONING 8 4 BUS1000 Busbar Protection GEK 98514B ...
Page 56: ...9 TESTS AND PERIODICAL MAINTENANCE 9 2 BUS1000 Busbar Protection GEK 98514B ...
Page 66: ...10 FIGURES 10 10 BUS1000 Busbar Protection GEK 98514B ...
Page 74: ...11 DIMENSIONS 11 8 BUS1000 Busbar Protection GEK 98514B FIGURE 23 CABINET 226B2211F21 ...
Page 104: ...13 SCHEMATICS DOUBLE BUSBAR 13 16 BUS1000 Busbar Protection GEK 98514B ...