Section 23 - Appendix C – Monitor Options for PWA 86739-01
57
23.2 Main Board Option Settings
All monitor option jumpers for the Dual Vibration Monitor are on the Main Board. The
following table lists these options and their jumper positions.
Option Settings on Older Version of the Main Board (Part Number 86739-01)
JUMPER
OPTION
SETTING
INSTALL REMOVE
First Out
Enabled *
Disabled
W13G
----------
----------
W13G
Alert Mode
Latching *
Nonlatching
W13B
----------
----------
W13B
Danger Mode
Latching *
Nonlatching
W13A
----------
----------
W13A
Danger Voting
And Relay Drive
Or Relay Drive *
W13F
----------
----------
W13F
Danger Bypass Switch
Enabled
Disabled *
W13E
----------
----------
W13E
Vibration Alarm Delay **
0.1 s.
1 s.
3 s. *
6 s.
----------
W13D
W13C
W13C, D
W13C, D
W13C
W13D
----------
Gap Alarm
Enabled
Disabled *
W12A
----------
----------
W12A
Recorder Clamping Mode
+4 to 20 mA Rec. only
NOT OK = 4 mA
NOT OK = 2 mA*
----------
W9B, W10D
W9B, W10D
----------
Corner Frequency Option
60-36,000 RPM
240-240,000 RPM*
W3, W5D,
W7B
W5E, W7A
W5E, W7A
W3, W5D,
W7B
* Standard configuration as shipped from factory.
** Gap Alarm Delay is 6 s.