3300/16 Dual Vibration Monitor Operation Manual
48
21.6 Transducer Input Options
To set the transducer input option, remove jumpers W15I, J, K, L, M, N, O, P / W20M, N.
Install jumpers specified in following table.
Transducer Input Options
Transducer Input
Install
Jumpers
-01
3300 8mm, 3300XL 8mm or
7200 5 & 8mm Proximitor
®
Sensor
(200 mV/mil)
W15I, J, M, N
-02 & -05
3000 or
3300 RAM Proximitor
®
Sensor
(200 mV/mil)
W15I, J, K, O
W20M, N
-03
7200 11mm Proximitor
®
Sensor
(100 mV/mil)
W15L, P
W20N
-04
3300 HTPS 16mm or 3300 XL 11mm or
7200 14mm Proximitor
®
Sensor
(100 mV/mil)
W15M, N
W20M
21.7 Trip Multiply
The following jumpers control the Trip Multiply feature:
• W15Q, R, S, T
• W17K, L, M, N
• W20O, P
Note
These jumpers are labeled "Do Not Change" on the
PWA because careful thought must be given to
changing the Trip Multiply configuration. Alarm
setpoints will be multiplied by 2 or 3.