31
Valve Actions Menu
1. Bypass Mode
In some cases a valve may need the solenoid on or off when in a full closed or full open position. The
DNGP has the ability to energize (turn on) or de-energize (turn off) the solenoid using the bypass mode.
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Valve Actions Menu
Loss of Signal
Bypass Mode
Pulse Mode
▼
▼
Bypass Mode:
Disabled
Enabled
Press UP or DOWN button
to select VALVE ACTIONS
then press ENTER button
Press UP or DOWN button
to select BYPASS MODE
then press ENTER button
Press UP or DOWN button
to make option selection
then press ENTER button
2. Pulse Mode
Pulse Mode is used for underdamped dynamic systems such as compressor recycle valve application.
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Valve Actions Menu
Loss of Signal
Bypass Mode
Pulse Mode
▼
▼
Pulse Mode
Threshold
On Time
Off Time
Press UP or DOWN button
to select VALVE ACTIONS
then press ENTER button
Press UP or DOWN button
to select PULSE MODE
then press ENTER button
Press UP or DOWN button
to make option selection
then press ENTER button
Default Values
Threshold: 5%
On Time:
70 ms
Off Time:
80 ms
*Setting Threshold to 0% disables Pulse Mode