30
Input Confi guration Menu
1. Input Select
It is sometimes desirable to change the input of the DNGP from standard 4-20 mA to user defined digital
inputs, or Modbus Control. This can be accomplished through the INPUT CONFIGURATION MENU using
the INPUT SELECT option. The diagram below, and on the following pages, show the actual process
needed to configure the inputs of the DNGP when already operating from the TOP LEVEL SETUP SCREEN
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Input Config Menu
Input Selections
Split Control
Positioner Action
▼
▼
Input Selection
4-20 mA Curr Loop
Digital Inputs
Modbus Control
Press UP or DOWN button
to select INPUT CONFIG,
then press ENTER button
Press UP or DOWN button
to select INPUT SELECT
then press ENTER button
Press UP or DOWN button
to make option selection
then press ENTER button
2. Split Control
In some applications, split range control is needed instead of the standard 4-20 mA range. The DNGP can be
accomplish this feat through the INPUT CONFIGURATION MENU using the SPLIT CONTROL option. The DNGP
has the option to enable or disable the split control feature or set the upper and lower split limits with 4 mA
minimum range in 1 mA increments.
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Input Config Menu
Input Selections
Split Control
Positioner Action
▼
▼
Split Control Menu
Enable or Disable
Set Upper Limit
Set Lower Limit
Press UP or DOWN button
to select INPUT CONFIG,
then press ENTER button
Press UP or DOWN button
to select SPLIT CONTROL
then press ENTER button
Press UP or DOWN
button to select
UPPER LIMIT then
press ENTER button
Press UP or DOWN
button to select
LOWER LIMIT then
press ENTER button
Upper Split Limit
16 mA
Lower Split Limit
12 mA