5. Dehumidification Operation Mode
•
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
•Hot-Start Control
•
The indoor fan stops until the indoor pipe temperature reaches 82
0
F.
•
During heating operation, if indoor pipe temperature falls below 78
0
F., fan stops.
•
The operation diagram is shown below.
INDOOR PIPE
TEMP.
INDOOR FAN SPEED
COMPRESSOR
OFF
LOW
Selection
fan speed
OFF
ON
1 min
82 F
0
78 F
0