AL-1291 Point ID DGP
Installation Manual
16
Location 5
Use this location to program output supervision for IO devices.
shows the available programming
options.
The default setting for the 4I4O device is a binary code of 00001111, or a decimal setting of 15. This indicates
that outputs 5 to 8 are set to 0 (disabled) and outputs 1 to 4 are set to 1 (enabled). Outputs 5 to 8 are reserved for
future use and can not be changed. To change the default for outputs 1 to 4, change the single digit assigned to
the output in the binary code. For example, reading the binary code from right to left (bits 0 to 7), the first digit
on the right indicates the setting for ouput 1. If you need output 1 to be set to
0
(disabled), change the binary
code to 0000111
0
.
Location 6
Location 6 is reserved for future programming options. Press
Enter
to scroll to the next location.
Location 7
Location 7 is reserved for future programming options. Press
Enter
to scroll to the next location.
Location 8
Location 8 is a read-only location that indicates the EOL (end-of-line) value. The default setting is 47K, which
has a binary value of 00000101 and a decimal value of 5. Do not change the default values. Press
Enter
to
scroll to the next location.
Location 9
Location 9 is a read-only location that indicates the number of inputs and outputs. The values are set by the
DGP. Do not change the default values. Press
Enter
to scroll to the next location.
Table 8.
Location 5 setting options
Output 4 (bit 3)
Output 3 (bit 2)
Output 2 (bit 1)
Output 1 (bit 0)
0 = disabled
0 = disabled
0 = disabled
0 = disabled
1 = enabled
1 = enabled
1 = enabled
1 = enabled