SECTION 1 4-MicroVersaTrip® Plus and Micro Versa Trip® PM Trip Units
FIG. 1 1 5
1 4.5 PHASE CURRENT SENSORS
The current sensors supply the power and signal input
necessary to operate the trip system Fig. 1 1 6 shows the
fixed phase sensors available. The sensors have a po
�
ar
ity associated with their windings. The com�on t�rm1�al
of the sensor is the right hand terminal. A wh1te w1re With
a push-on terminal will be connected to thi� common
terminal. All phase sensors must be correctly w1red for the
programmer summing circuitry to function properly.
80
TAPPED
FIG. 1 1 6
COMMON
TERM I NAL
The fixed phase sensors are available with an additional
winding. This winding is brought out to separate fla�
terminals. These phase sensors are used when the hi
level instantaneous ('H'-option) is required. Fig. 1 1 7
shows an ' H ' -option phase sensor. When the ' H '-option
phase sensor is installed, there are four leads connected
to it. There is no polarity associated with the 'H'-option
windings.
FIG. 1 1 7 'H'-OPTION PHASE SENSOR