P50 Agile P153
7 Protection Parameter Settings
P153/EN M/B
7-7
Sr. No
Parameter
Defaults setting
Setting / Ranges
5.
Copy To
No Operation
No Operation / Group 1 / Group 2
This command allows the displayed settings to be copied to a selected setting group.
6.
Setting Group 1
Enabled
Enabled / Disabled
This setting enables or disables settings Group 1. If the Setting Group 1 is enabled from the configuration setting, then all associated
settings and signals are available in Group 1 setting menu. If the Setting Group1 is disabled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
7.
Setting Group 2
Disabled
Enabled / Disabled
This setting enables or disables settings Group 2. If the Setting Group 2 is enabled from the configuration setting, then all associated
settings and signals are available in Group 2 setting menu. If the Setting Group 2 is disabled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
8.
System Config
Disabled
Enabled / Disabled
This setting hides or unhides the System Config menu. Inside the 2nd Harmonic blocking related parameters are present
9.
Overcurrent
Enabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Phase Overcurrent Protection function. If disabled, then all associated settings and
signals are hidden, with the exception of this setting. Same for all other Items.
10.
Neg Sequence O/C
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Negative Sequence Overcurrent Protection.
11.
Broken Conductor
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Broken Conductor Protection.
12.
Earth Fault 1
Enabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Measured Earth Fault Protection function
13
Earth Fault 2
Enabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Derived Earth Fault Protection function.
14.
Thermal Overload
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Thermal Overload function.
15.
Cold Load Pickup
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Cold Load Pickup function.
16.
Measure’t Setup
ABC
ABC /RYB
This setting determines the representation of Phases. Based on this setting, the representation in measurements, records etc shall
change. No change is expected for the stored records, (if any)
17.
UnderCurr Prot
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the Under Current Protection.
18.
CB Fail
Disabled
Enabled / Disabled
This setting enables (activate) or disables (turn off) the CB Fail Protection.
19.
Setting Values
Secondary
Primary/Secondary
This setting determines the reference for all settings dependent on the transformer ratios; either referenced to the primary or the
secondary.
2.5
TRANS. RATIOS Settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to zzzz
This setting specifies to enter the set password
2.
Phase CT Primary
100 A
1 to 30000A step 1A
This setting determines the phase current transformer input primary current rating.
3.
Phase CT Sec’y
1 A
1A or 5A
This setting determines the phase current transformer input secondary current rating.
Summary of Contents for Agile P153
Page 3: ...P50 Agile P153 1 Introduction P153 EN M B 1 1 INTRODUCTION CHAPTER 1 ...
Page 4: ...1 Introduction P50 Agile P153 1 2 P153 EN M B ...
Page 10: ...1 Introduction P50 Agile P153 1 8 P153 EN M B ...
Page 11: ...P50 Agile P153 2 Safety Information P153 EN M A 2 1 SAFETY INFORMATION CHAPTER 2 ...
Page 22: ...Chapter 2 Safety Information P50 Agile P153 2 12 P153 EN M A ...
Page 23: ...P50 Agile P153 3 Hardware Design P153 EN M B 3 1 HARDWARE DESIGN CHAPTER 3 ...
Page 24: ...3 Hardware Design P50 Agile P153 3 2 P153 EN M B ...
Page 32: ...3 Hardware Design P50 Agile P153 3 10 P153 EN M B ...
Page 33: ...P50 Agile P153 4 Front Panel P153 EN M B 4 1 FRONT PANEL CHAPTER 4 ...
Page 34: ...4 Front Panel P50 Agile P153 4 2 P153 EN M B ...
Page 39: ...P50 Agile P153 5 Configuration P153 EN M B 5 1 CONFIGURATION CHAPTER 5 ...
Page 40: ...P50 Agile P153 5 Configuration P153 EN M B 5 2 ...
Page 150: ...P50 Agile P153 5 Configuration P153 EN M B 5 112 ...
Page 151: ...P50 Agile P153 6 Protection Functions P153 EN M B 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Page 152: ...6 Protection Functions P50 Agile P153 6 2 P153 EN M B ...
Page 168: ...7 Protection Parameter Settings P50 Agile P153 7 2 P153 EN M B ...
Page 189: ...P50 Agile P153 8 Monitoring Control P153 EN M B 8 1 MONITORING CONTROL CHAPTER 8 ...
Page 190: ...8 Monitoring Control P50 Agile P153 8 2 P153 EN M B ...
Page 207: ...P50 Agile P153 9 SCADA Communications P153 EN M B 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Page 208: ...12 SCADA Communications P50 Agile P153 9 2 P153 EN M B ...
Page 220: ...12 SCADA Communications P50 Agile P153 9 14 P153 EN M B ...
Page 221: ...P50 Agile P153 10 Installation P153 EN M B 10 1 INSTALLATION CHAPTER 10 ...
Page 222: ...10 Installation P50 Agile P153 10 2 P153 EN M B ...
Page 234: ...13 Commissioning Instructions P50 Agile P153 13 2 P153 EN M B ...
Page 242: ...12 Maintenance and Troubleshooting P50 Agile P153 12 2 P153 EN M B ...
Page 250: ...12 Maintenance and Troubleshooting P50 Agile P153 12 10 P153 EN M B ...
Page 252: ...13 Technical Specifications P50 Agile P153 13 2 P153 EN M B ...
Page 263: ...P50 Agile P153 14 Wiring Diagrams P153 EN M B 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Page 264: ...14 Wiring Diagrams P50 Agile P153 14 2 P153 EN M B ...
Page 267: ......