
6 Protection Functions
P50 Agile P153
6-8
P153/EN M/B
However, certain faults may arise which can remain undetected by such schemes. Negative
Sequence Overcurrent elements can be used in such cases.
Any unbalanced fault condition will produce a negative sequence current component. Therefore, a
negative phase sequence overcurrent element can be used for both phase-to-phase and phase-to-
earth faults.
Negative Sequence Overcurrent protection offers the following advantages:
•
Negative phase sequence overcurrent elements are more sensitive to resistive phase-to-phase
faults, where phase overcurrent elements may not operate.
•
In certain applications, residual current may not be detected by an earth fault element due to the
s
ystem configuration. For example, an earth fault element applied on the delta side of a delta-
star transformer is unable to detect earth faults on the star side. However, negative sequence
current will be present on both sides of the transformer for any fault condition, irrespective of the
transformer configuration. Therefore, a negative phase sequence overcurrent element may be
used to provide time-delayed back-up protection for any uncleared asymmetrical faults
downstream.
•
Where rotating machines are protected by fuses, loss of a fuse produces a large amount of
negative sequence current. This is a dangerous condition for the machine due to the heating
effect of negative phase sequence current. An upstream negative phase sequence overcurrent
element could therefore be applied to provide back-up protection for dedicated motor protection
relays.
•
It may be sufficient to simply trigger an alarm to indicate the presence of negative phase
sequence currents on the system. Operators may then investigate the cause of the imbalance.
2.3.1
Negative Sequence Overcurrent Protection Implementation
Negative Sequence Overcurrent Protection is implemented in the
NEG SEQUENCE O/C
column of
the relevant settings group.
The product provides three stages of negative sequence overcurrent protection with independent time
delay characteristics.
Stages 1, 2 and 3 provide a choice of operate and reset characteristics, where you can select
between:
•
A range of standard IDMT (Inverse Definite Minimum Time) curves
•
DT (Definite Time)
This is achieved using the cells
•
I2>
(n)
Function
for the overcurrent operate characteristic
•
I2>
(n)
Reset Char
for the overcurrent reset characteristic
where (n) is the number of the stage.
The IDMT-capable stages, (1, 2 and 3) also provide a Timer Hold facility. This is configured using the
cells
I2>
(n)
tRESET
, where (n) is the number of the stage. Timer Hold facility is applicable for both
IEC and IEEE curves. IEEE & US curves have IDMT reset curve option in addition to DT
.
2.3.2
Negative Sequence Overcurrent Protection Logic
For Negative Phase Sequence Overcurrent Protection, the energising quantity I2> is compared with
the threshold current
I2>
(n)
Current Set
. If the value exceeds this setting a Start signal (Strt I2>(n)) is
generated, provided there are no blocks. 5% hysteresis is built into the comparator such that the drop-
off value is 0.95 x of the current set threshold.
Summary of Contents for Agile P153
Page 3: ...P50 Agile P153 1 Introduction P153 EN M B 1 1 INTRODUCTION CHAPTER 1 ...
Page 4: ...1 Introduction P50 Agile P153 1 2 P153 EN M B ...
Page 10: ...1 Introduction P50 Agile P153 1 8 P153 EN M B ...
Page 11: ...P50 Agile P153 2 Safety Information P153 EN M A 2 1 SAFETY INFORMATION CHAPTER 2 ...
Page 22: ...Chapter 2 Safety Information P50 Agile P153 2 12 P153 EN M A ...
Page 23: ...P50 Agile P153 3 Hardware Design P153 EN M B 3 1 HARDWARE DESIGN CHAPTER 3 ...
Page 24: ...3 Hardware Design P50 Agile P153 3 2 P153 EN M B ...
Page 32: ...3 Hardware Design P50 Agile P153 3 10 P153 EN M B ...
Page 33: ...P50 Agile P153 4 Front Panel P153 EN M B 4 1 FRONT PANEL CHAPTER 4 ...
Page 34: ...4 Front Panel P50 Agile P153 4 2 P153 EN M B ...
Page 39: ...P50 Agile P153 5 Configuration P153 EN M B 5 1 CONFIGURATION CHAPTER 5 ...
Page 40: ...P50 Agile P153 5 Configuration P153 EN M B 5 2 ...
Page 150: ...P50 Agile P153 5 Configuration P153 EN M B 5 112 ...
Page 151: ...P50 Agile P153 6 Protection Functions P153 EN M B 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Page 152: ...6 Protection Functions P50 Agile P153 6 2 P153 EN M B ...
Page 168: ...7 Protection Parameter Settings P50 Agile P153 7 2 P153 EN M B ...
Page 189: ...P50 Agile P153 8 Monitoring Control P153 EN M B 8 1 MONITORING CONTROL CHAPTER 8 ...
Page 190: ...8 Monitoring Control P50 Agile P153 8 2 P153 EN M B ...
Page 207: ...P50 Agile P153 9 SCADA Communications P153 EN M B 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Page 208: ...12 SCADA Communications P50 Agile P153 9 2 P153 EN M B ...
Page 220: ...12 SCADA Communications P50 Agile P153 9 14 P153 EN M B ...
Page 221: ...P50 Agile P153 10 Installation P153 EN M B 10 1 INSTALLATION CHAPTER 10 ...
Page 222: ...10 Installation P50 Agile P153 10 2 P153 EN M B ...
Page 234: ...13 Commissioning Instructions P50 Agile P153 13 2 P153 EN M B ...
Page 242: ...12 Maintenance and Troubleshooting P50 Agile P153 12 2 P153 EN M B ...
Page 250: ...12 Maintenance and Troubleshooting P50 Agile P153 12 10 P153 EN M B ...
Page 252: ...13 Technical Specifications P50 Agile P153 13 2 P153 EN M B ...
Page 263: ...P50 Agile P153 14 Wiring Diagrams P153 EN M B 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Page 264: ...14 Wiring Diagrams P50 Agile P153 14 2 P153 EN M B ...
Page 267: ......