7.1.1 Mains Supply High Power
Mains Supply 3 x 380 - 480 VAC
Typical Shaft output at
400 V [kW]
110
132
160
200
250
Typical Shaft output at
460 V [HP]
150
200
250
300
350
Unit Size IP21
41
41
42
42
42
Unit Size IP54
41
41
42
42
42
Unit Size IP00
43
43
44
44
44
Output current
Continuous
(at 400 V) [A]
212
260
315
395
480
Intermittent (60 sec
overload)
(at 400 V) [A]
233
286
347
435
528
Continuous
(at 460 V) [A]
190
240
302
361
443
Intermittent (60 sec
overload)
(at 460 V) [A]
209
264
332
397
487
Continuous KVA
(at 400 V) [KVA]
147
180
218
274
333
Continuous KVA
(at 460 V) [KVA]
151
191
241
288
353
Max. input current
Continuous
(at 400 V ) [A]
204
251
304
381
463
Continuous
(at 460 V) [A]
183
231
291
348
427
Max. cable size, mains
motor and load share
[mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses
[A]
1
300
350
400
500
600
Estimated power loss
at rated max. load [W]
4)
3234
3782
4213
5119
5893
Weight,
Unit Size IP21, IP 54 [kg]
96
104
125
136
151
Weight,
Unit Size IP00 [kg]
82
91
112
123
138
Efficiency
4)
0.98
Output frequency
0 - 800 Hz
Heatsink overtemp. trip
85
°
C
90
°
C
105
°
C
105
°
C
115
°
C
Power card ambient trip
60
°
C
AF-600 FP Design Guide
138
7
Summary of Contents for AF-600 FP Series
Page 11: ...AF 600 FP Design Guide 10 2...
Page 45: ...AF 600 FP Design Guide 44 3...
Page 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Page 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Page 95: ...AF 600 FP Design Guide 94 5...
Page 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Page 105: ...AF 600 FP Design Guide 104 6...