4.3 Final Set-Up and Test
To test the set-up and ensure that the frequency converter is running, follow these steps.
Step 1. Locate the motor name plate
NB!
The motor is either star- (Y) or delta- connected (
∆
). This information is lo-
cated on the motor name plate data.
Step 2. Enter the motor name plate data in this parameter list.
To access this list first press the [QUICK MENU] key then select “Q2 Quick
Setup”.
1.
Motor Power [kW]
or Motor Power [HP]
par. P-07
Motor Power [kW]
par. P-02
Motor Power [HP]
2.
Motor Voltage
par. F-05
Motor Rated Volt-
age
3.
Motor Frequency
par. F-04
Base Frequency
4.
Motor Current
par. P-03
Motor Current
5.
Motor Nominal Speed
par. P-06
Base Speed
Step 3. Activate the Auto Tune
Performing an auto tune will ensure optimum performance. The auto tune measures the values from the motor model equivalent diagram.
1.
Activate the auto tune par. P-04
Auto Tune
.
2.
Choose between complete or reduced auto tune. If an LC filter is mounted, run only the reduced auto tune, or remove the LC filter during the auto tune
procedure.
3.
Press the [OK] key. The display shows “Press [Hand] to start”.
4.
Press the [Hand] key. A progress bar indicates if the auto tune is in progress.
AF-600 FP Design Guide
82
4
Summary of Contents for AF-600 FP Series
Page 11: ...AF 600 FP Design Guide 10 2...
Page 45: ...AF 600 FP Design Guide 44 3...
Page 51: ...Do not combine low voltage parts and PELV systems AF 600 FP Design Guide 50 3...
Page 58: ...4 How to Install AF 600 FP Design Guide 57 4...
Page 95: ...AF 600 FP Design Guide 94 5...
Page 102: ...5 1 11 Fixed Variable Speed Pump Wiring Diagram AF 600 FP Design Guide 101 5...
Page 105: ...AF 600 FP Design Guide 104 6...