6.10.5 Preset Single Register (06 HEX)
Description
This function presets a value into a single holding register.
Query
The query message specifies the register reference to be preset. Register addresses start at zero, i.e. register 1 is addressed as 0.
Example: Write to H-40, register 4400.
Field Name
Example (HEX)
Slave Address
01
Function
06
Register Address HI
11 (Register address 4399)
Register Address LO
2F (Register address 4399)
Preset Data HI
00
Preset Data LO
01
Error Check (CRC)
-
Response
Response The normal response is an echo of the query, returned after the register contents have been passed.
Field Name
Example (HEX)
Slave Address
01
Function
06
Register Address HI
11
Register Address LO
2F
Preset Data HI
00
Preset Data LO
01
Error Check (CRC)
-
AF-600 FP Design Guide
126
6