3.1.14 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC 60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the drive voltage rating. With the proper fusing the drive short circuit current rating (SCCR) is
100,000 Arms.
AF-600 3-phase
Recommended fuse size
Recommended max fuse
Recommended circuit breaker
Max trip level
[HP]
[A]
1
gG-16
gG-25
PKZM0-25
25
2
3
5
gG-20
gG-32
7,5
gG-50
gG-63
PKZM4-50
50
10
15
20
gG-80
gG-125
NZMB1-A100
100
25
30
gG-125
gG-150
NZMB2-A200
150
40
aR-160
aR-160
50
aR-200
aR-200
NZMB2-A250
250
60
aR-250
aR-250
Table 3.2 200-240V, IP20/Open Chassis
AF-600 3-phase
Recommended fuse size
Recommended max fuse
Recommended circuit breaker
Max trip level
[HP]
[A]
1
gG-20
gG-32
PKZM0-25
25
2
3
5
7,5
gG-63
gG-80
PKZM4-63
63
10
15
20
gG-80
gG-100
NZMB1-A100
100
25
gG-125
gG-160
NZMB2-A200
160
30
40
aR-160
aR-160
50
aR-200
aR-200
NZMB2-A250
250
60
aR-250
aR-250
Table 3.3 200-240V, IP55/Nema 12
Electrical Installation
AF-600 FP High Power Operating Instructions
20
3
3