Recommended max. fuse
AF-600 1-
phase
AF-600 3-
phase
Bussmann
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
HP
HP
Type JFHR2
2)
Type JFHR2
Type JFHR2
4)
Type J
1
FWX-10
-
-
HSJ-10
2
FWX-15
-
-
HSJ-15
2
3
FWX-20
-
-
HSJ-20
3
5
FWX-30
-
-
HSJ-30
5
7.5-10
FWX-50
-
-
HSJ-50
7.5
15
FWX-60
-
-
HSJ-60
10
20
FWX-80
-
-
HSJ-80
25-30
FWX-125
-
-
HSJ-125
20
40
FWX-150
L25S-150
A25X-150
HSJ-150
30
50
FWX-200
L25S-200
A25X-200
HSJ-200
60
FWX-250
L25S-250
A25X-250
HSJ-250
Table 3.10 200-240V
1) KTS-fuses from Bussmann may substitute KTN for 240V frequency converters.
2) FWH-fuses from Bussmann may substitute FWX for 240V frequency converters.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V frequency converters.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V frequency converters.
Recommended max. fuse
AF-600
1-phase
AF-600
3-phase
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[HP]
[HP]
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
1
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-6
LP-CC-6
2-3
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
5
KTS-R-20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
7.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
10
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
15-20
KTS-R-40
JKS-40
JJS-40
-
-
-
25
KTS-R-50
JKS-50
JJS-50
-
-
-
10
30
KTS-R-60
JKS-60
JJS-60
-
-
-
15
40
KTS-R-80
JKS-80
JJS-80
-
-
-
50
KTS-R-100
JKS-100
JJS-100
-
-
-
60
KTS-R-125
JKS-125
JJS-125
-
-
-
25
75
KTS-R-150
JKS-150
JJS-150
-
-
-
50
100
KTS-R-200
JKS-200
JJS-200
-
-
-
125
KTS-R-250
JKS-250
JJS-250
-
-
-
Table 3.11 380-480V, 125HP and below
Electrical Installation
AF-600 FP High Power Operating Instructions
26
3