5.2 Network Drive Control Inputs and -Outputs
5.2.1 Analog Input- and Output Objects
Control the drive from the BACnet network using 'objects'. The various types of 'objects' and their descriptions are shown in the following tables.
Object ID
Object Name
Read/Write
Changeable
Description
Non volatile ram
Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus time-
out
AI:0
Analog
Input 53
R
Yes
No
DR-62
Yes
NO
AI:1
Analog
Input 54
R
Yes
No
DR-64
Yes
NO
AI:2
Analog
In X30/11
R
Yes
No
DR-75
Yes
NO
AI:3
Analog
In X30/12
R
Yes
No
DR-76
Yes
NO
AI:4
Analog
Input X42/1
R
Yes
No
LG-30
Yes
NO
AI:5
Analog
Input X42/3
R
Yes
No
LG-31
Yes
NO
AI:6
Analog
Input X42/5
R
Yes
No
LG-32
Yes
NO
Table 5.1: Analog inputs
Object ID
Object Name
Read/Write
Changeable
Description
Non volatile ram
Store
Linked to AF-600
FPParameter
Alarm
notifi-
cation
Triggers Bus
Timeout
AO:0
Terminal
42 Output Bus Control
W/R
Yes
No
AN-53
No
Yes
AO:1
Pulse out
#27 Bus
Control
W/R
Yes
No
E-93
No
Yes
AO:2
Pulse out
#29 Bus
Control
W/R
Yes
No
E-95
No
Yes
AO:3
Analogue
Out X30/8 [mA]
W/R
Yes
No
AN-63
No
Yes
AO:4
Analogue
output
X42/7[V]
W/R
Yes
No
AO-43
No
Yes
AO:5
Analogue
output
X42/9[V]
W/R
Yes
No
AO-53
No
Yes
AO:6
Analogue
output
X42/11[V]
W/R
Yes
No
AO-63
No
Yes
Table 5.2: Analog outputs