4 How to Configure the System
4.1 Configuring BACnet
4.1.1 Initialization Procedure
The Initialization Procedure is explained by the flow chart given below:
Initialization Parameter
General Settings
Name
Parameter Number
Default Value
Setting for BACnet
Control Site
O-01
Digital and control word
Digital and control word
Control word source
O-02
Drive RS-485
Drive RS-485
ControlWord Timeout time
O-03
1.0 sec
1.0 sec
ControlWord Timeout Function
O-04
Off
Off
End of Timeout Function
O-05
Resume setup
Resume setup
Reset ControlWord Timeout
O-06
Do not reset
Do not reset
Diagnosis
O-07
Set up
Don’t care
ControlWord Profile
O-10
Drive protocol
Drive protocol
Drive Port Settings
Name
Parameter Number
Default Value
Setting for BACnet
Protocol
O-30
Drive
Drive Option
Address
O-31
1
1
Baud Rate
O-32
9600 baud
9600 baud
Minimum Response Delay
O-35
10 ms
10 ms
Max Response Delay
O-36
5000 ms
5000 ms
Table 4.1: 1) Please see also section: Parameter Overview >Parameter List.