4–12
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
A3 RECORDS
CHAPTER 4: ACTUAL VALUES
Second and fifth harmonic per-phase differential current. All per Winding 1 and 2. The
Event Recorder can be cleared from
ACTUAL VALUES > A3 RECORDS > CLEAR EVENT REC
setpoint. The following table provides a list of the event types:
Table 4-2: Event type
For a complete list of Event Causes, see Format Code FC134 in the
3 Series
Communications Guide
. Note that the format codes differ for each relay model.
Transient records
PATH
:
ACTUAL VALUES > A3 RECORDS > TRANSIENT RECORDS
FORCE TRIGGER?
No
Range: No, Yes
TOTAL RECORDS
1
Range: N/A
AVAILABLE RECORDS
1
Range: N/A
LAST CLEARED
Feb 08 2009
Range: N/A
Event Type
Display
Description
General Events
None
Events that occur when specific
operation takes place
Pickup Events
PICKUP:
These are events that occur when a
protection element picks up
Trip Events
TRIP:
These are events that occur when a
breaker trip is initiated
Alarm and Latched Alarm Events ALARM:
These are events that occur when an
alarm is initiated
Control Events
CONTROL:
These are events that occur when a
control element is activated
Dropout Events
DROPOUT:
These are events that occur when a
protection element drops out after a
corresponding pickup event
Contact Input Events
C. INPUT:
These are events that occur when a
contact input changes its state
Virtual Input Events
V. INPUT
These are events that occur when a
virtual input changes its state
Remote Input Events
R. INPUT
These are events that occur when a
remote input changes its state
Logic Element Events
L. ELEMENT
These are events that occur when a logic
element changes its state
Self-Test Warning Events
SELF-TEST WARNING These are events that occur when a self-
test warning is detected.
Block Events
BLOCK:
These are events that occur upon
activation of any block signal.
Setting Date/Time Events
GENERAL:
These are events that occur upon
changing the date or time in the relay.