6–30
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S2 SYSTEM SETUP
CHAPTER 6: SETPOINTS
D/d180°
1
DELTA (gnd 1/2)
180° lag
D/d240°
1
DELTA (gnd 1/2)
240° lag
2
DELTA (gnd 2/3)
180° lag
0°
2
DELTA (gnd 2/3)
240° lag
0°
D/d300°
1
DELTA (gnd 1/2)
300° lag
D/y30°
1
DELTA (gnd 1/2)
0°
2
DELTA (gnd 2/3)
300° lag
0°
2
WYE (gnd 2/3) 30°
lag
330° lag
D/y150°
1
DELTA (gnd 1/2)
0°
D/y210°
1
DELTA (gnd 1/2)
0°
2
WYE (gnd 2/3) 150°
lag
210° lag
2
WYE (gnd 2/3) 210°
lag
150° lag
D/y330°
1
DELTA (gnd 1/2)
0°
Y/z30°
1
WYE (gnd 1/2)
30° lag
2
WYE (gnd 2/3) 330°
lag
30° lag
2
ZIG-ZAG (gnd 2/3)
30° lag
0°
Y/z150°
1
WYE (gnd 1/2)
150° lag
Y/z210°
1
WYE (gnd 1/2)
210° lag
2
ZIG-ZAG (gnd 2/3)
150° lag
0°
2
ZIG-ZAG (gnd 2/3)
210° lag
0°
Transformer
Type
Wdg.
Connection
Voltage
Phasors
Phase
Shift
(
Φ
comp
)
Transformer
Type
Wdg.
Connection
Voltage
Phasors
Phase
Shift
(
Φ
comp
)