CHAPTER 4: ACTUAL VALUES
A1 STATUS
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
4–3
RELAY 1 TRIP (Output Relay #1)
OFF
Range: Off, On
The “ON” state of Output Relay #1 (W1 TRIP) shows that a TRIP command has been sent
to the W1 breaker.
RELAY 2 TRIP (Output Relay #2)
OFF
Range: Off, On
The “ON” state of Output Relay #2 (W2 TRIP) shows that a TRIP command has been sent
to the W2 breaker.
OUTPUT RELAY 3 to 6 (Auxiliary Output Relays)
OFF
Range: Off, On
OUTPUT RELAY 7 (Critical Failure Relay)
Range: Off, On
The "ON" state indicates that the relay is in-service.
Logic elements
PATH
:
ACTUAL VALUES > A1 STATUS > LOGIC ELEMENTS
LOGIC ELEMENT 1 to 16
OFF
Range: Off, On
The state “ON” or “OFF” for each logic element depends on its programmed logic:
triggering inputs, blocking inputs, plus any pickup, and/or reset time delay.
Virtual inputs
The state of all active virtual inputs is displayed here.
PATH
:
ACTUAL VALUES > A1 STATUS > VIRTUAL INPUTS
VIRTUAL INPUTS 1 to 32
OFF
Range: Off, On
Remote inputs
The state of all active remote inputs is displayed here.
PATH
:
ACTUAL VALUES > A1 STATUS > REMOTE INPUTS
REMOTE INPUTS 1 to 32
OFF
Range: Off, On
Remote outputs
The state of all active remote outputs is displayed here.
PATH
:
ACTUAL VALUES > A1 STATUS > REMOTE OUTPUTS
REMOTE OUTPUTS 1 to 32
OFF
Range: Off, On