7–14
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
M4 BREAKER MONITOR
CHAPTER 7: MAINTENANCE
M4 Breaker monitor
The status of the breaker trip and close coils, as well as the trip and close circuits, can be
monitored under
MAINTENANCE > M4 W1 (W2) BKR MONITOR
. In the case where a
breaker coil or circuit fails, the relay will display the message "Unhealthy" for the
corresponding coil.
Further information on the breaker is provided under
BKR TRIP COUNTER
, where the
345 stores the number of trips. The counter can be reset under
M3 RESET COUNTERS >
RST BKR TRIP COUNT
set to "Yes".
PATH
:
MAINTENANCE > M4 W1 (W2) BKR MONITOR
W1 (W2) BKR TRIP COIL
Healthy
Range: Healthy, Unhealthy
W1 (W2) BKR TRIP COUNTER
5
Range: 0 to 10000 trips
W1 (W2) BKR ALARM COUNTER
5
Range: 0 to 10000 trips
W1 (W2) LAST TRIP TIME
5
Range: 0 to 10000 ms
W1 (W2) AVG TRIP TIME
5
Range: 0 to 10000 ms
W1 (W2) LAST CLOSE TIME
5
Range: 0 to 10000 ms
W1 (W2) AVG CLOSE TIME
5
Range: 0 to 10000 ms
W1 (W2) LAST CHARGE TIME
5
Range: 0 to 60000 ms
W1 (W2) AVG CHARGE TIME
5
Range: 0 to 60000 ms