96
MDS™ Master Station
MDS 05-6399A01, Rev. F
6.2 DC Power Supply Module
Figure 6-2. DC Power Supply Module
Including:
03-6843A01: +/- 12-36 VDC
03-6844A01: +/- 36-75 VDC
03-6845A01: +/- 75-140 VDC
Table 6-3. DC Power Supply Module (6843, 6844, 6845) Specifications:
Supply Type
SMPS DC to DC
Input Voltage Range
+/-36-75 VDC, input is isolated from ground
+/-12-36 VDC, input is isolated from ground
+/-75-140 VDC, input is isolated from ground
Output
24 VDC, 4.0 A
Line Frequency
DC Input only
Power Consumption
120W, Maximum
Protection
Integrated thermal protection, short circuit protection, internal fuse
Ambient Temperature range
Full capacity from -30°C to +60°C
CSA Certified operating range -30°C to +50°C
Master station power supply modules are field replaceable units that
can be removed from an operating system
so long as the input power
source to the module being replaced has been disconnected
. Refer to Section 8.4 Replacing
Modules for information on removal and installation.
DC power supply modules are available for several different input
ranges. These modules have interchangeable connectors. Make sure
the supply is within the rating for the module installed.
When installing DC Power Supply modules, torque thumbscrews to 10
in-lbs, or approximately ¼ turn past hand tight, to insure optimum heat
transfer through thermal contact connector on the rear of the unit.
When connecting DC Power Supply modules, the length of the power
cable
MUST