Page 9
RETROFIT CCW OPEN DAMPER
If the VVR is installed on a box which requires that the damper rotates COUNTER-CLOCKWISE to open, connect as
follows:
1.
Make sure the damper is closed, and the existing actuator is in the full
clockwise position.
2.
Connect the existing 3-wire floating actuator with 2-pair cable as shown in Figure 7.
3.
Set the address DIP switch as required per Appendix 1.
4.
Connect the low voltage power to the unit per the next section.
5.
Connect temperature sensors per additional sections of this manual.
6.
Connect fan or heating stages per additional sections of this manual.
7.
Connect modulating reheat valves per additional sections of this manual.
Figure 7: Wiring of Existing Actuator for Counter-Clockwise to Open
Actuator Wiring Connections for COUNTER-CLOCKWISE to open:
VVR COM
to
ACTUATOR COMMON
VVR CCW
to
ACTUATOR CCW
VVR CW
to
ACTUATOR CW
C
W
C
O
M
C
C
W
D
A
M
P
E
R
VVR BOARD
BLACK
WHITE
RED
RED
BLACK
WHITE
EXISTING 3-WIRE
ACTUATOR
C
O
M
C
C
W
C
W
2 PAIR CABLE
REFER TO ACTUATOR MANUFACTURER’S
INSTALLATION INSTRUCTION FOR SPECIFIC
DETAILS
IMPORTANT NOTE
THE SILKSCREEN ON THE VVR BOARD IS
INCORRECT. TO VERIFY - THE CCW
OUTPUT ENERGIZES ON A CALL TO OPEN ,
AND THE CW OUTPUT ENERGIZES TO
CLOSE.