Page 22
SPECIFICATIONS
Communication:
EIA RS-485 at 9600 baud on 22AWG shielded, plenum rated cable
(recommended Belden 6500FE or equivalent)
Power Requirements:
24VAC (-10% / 5%), 50/60/Hz
3.2VA for VAV
2.4VA plus actuator current for VVR
Recommend 5VA transformer sizing for AC power
Analog Inputs:
(3) 10K ohm thermistor
Type II.
Digital Inputs:
(2) Dry contacts
>/= 50ms timing
Analog Outputs:
(1) 0-10VDC
>/= 1K ohm drive impedance
Digital Outputs:
(4) Dry contacts
SPST pilot duty 1 amp at 24VAC or 24VDC
Environmental Limits:
Temperature:
32
o
F to 125
o
F.
Humidity (non-condensing):
95%
UL Listing:
ANSI/UL 916
Dimensions:
VAV:
9.0"W x 5.0"H x 2.5"D
VVR: 4.5"W x 4.0"H x 1.75"D
Shipping Weight:
VAV:
Approx. 1.95 lbs.
VVR: Approx. 0.5 lbs.