NEW INSTALLATION CW OPEN DAMPER
The VAV assembly operates whereas the Belimo actuator rotates CLOCKWISE to open the damper. To connect the
actuator to the damper shaft:
1.
Turn the damper to the closed position.
2.
Press the black triangular shaped clutch on the right edge of the actuator and
rotate the actuator fully counter-clockwise.
3.
Place the assembly over the damper shaft and hand-tighten the nuts on the
actuator V-clamp.
4.
Attach the assembly to the box or mounting plate by driving a sheet metal screw
through the eyelet on the terminal strip end of the assembly.
3.
Lock the actuator to the shaft by tightening the nuts on the V-clamp.
5.
Remove the VAV cover and set the address DIP switch as required per Appendix 1.
6.
Connect the low voltage power to the unit per the next section.
7.
Connect temperature sensors per additional sections of this manual.
8.
Connect fan or heating stages per additional sections of this manual.
9.
Connect modulating reheat valves per additional sections of this manual
NEW INSTALLATION CCW OPEN DAMPER
If the VAV is installed on a box which requires that the damper rotates COUNTER-CLOCKWISE to open, connect as
follows:
1.
Turn the damper to the closed position.
2.
Press the black triangular shaped clutch on the right edge of the actuator and
rotate the actuator fully clockwise.
3.
Place the assembly over the damper shaft and hand-tighten the nuts on the
actuator V-clamp.
4.
Attach the assembly to the box or mounting plate by driving a sheet metal screw
through the eyelet on the terminal strip end of the assembly.
5.
Remove the VAV cover and set the address DIP switch as required per Appendix 1.
6.
Connect the low voltage power to the unit per the next section.
7.
Remove and reverse connection of the RED and BLACK wires on the Belimo
actuator, where RED is connected to terminal 2 (CCW) and BLACK is connected
to terminal 3 (CW).
8.
Connect temperature sensors per additional sections of this manual.