GTD-1000Tx(M)
Instruction Manual
6. Detector Operation Flow
6. Detector Operation Flow
6.3. Operation Flow
6.4. Menu Configuration Table
■ Operation keys for detector system mode are defined as below.
[Figure 10. GTD-1000Tx(M) Mode Configuration]
ITEM
NAME
DESCRIPTION
FUNC
Function key
Detector Mode Setting Entry Function (Insert Magnetic-bar for 2 sec or longer in measuring mode)
Level2 Next stage entering function and setting saving function
RESET
Reset key
Move to the previous stage from the level entered.
↑
Up key
Next level mode that is configured in LEVEL1 and Change in Level2 setting Plus
↓
Down key
Next level mode that is configured in LEVEL1 and Change in Level2 setting Minus
LEVEL1
LEVEL2
DEFAULT
NAME
PARAMETER
PROGRAM
MODE
GAS TYPE (Gas Type)
[DEFIN./USER]
DEFIN.
GAS SEL(Gas Select)
Built-in gas name selection
COMB.
UNIT SEL (Unit Select)
%/%LEL/PPM/PPB
%LEL
D-POINT(Decimal Point)
0.100/1.00/10.0/100
100
HIGH SCL (High Scale)
1~10000
100
PASSWORD
00~99
00
CALIBRA.
MODE
(Calibration Mode)
CALIBRA.
[ZERO]
(Calibration Zero)
ZERO CAL
[NO,YES]
[NO]
ZERO GAS
[ 0]
ZERO >>>>
[SUCCESS / FAIL]
CAL. DATA
[ 0/ FAIL]
CALIBRA.
[SPAN]
(Calibration Span)
SPAN CAL
[NO , YES]
[NO]
SPAN GAS
[ 0]
SPAN SET
[ 50/ FAIL]
50
SPAN >>>>
[SUCCESS / FAIL ]
CAL. DATA
[ 0]
ALARM
MODE
ALM USED (Alarm Used)
[OFF / ON]
OFF
AL LATCH (Alarm Latch)
[OFF / ON]
OFF
A1 LEVEL (Alarm-1 Level)
[1 ~ 10000]
20
A1 TYPE (Alarm-1 Type)
[INC / DEC]
INC
A1 DBAND (Alarm-1 Dead Band)
[0.0 ~ 10.0%F.S]
0
A1 TIME (Alarm-1 Time)
[0~ 60]SEC
1
A2 LEVEL (Alarm-2 Level)
[1 ~ 10000]
40
A2 TYPE (Alarm-2 Type)
[INC / DEC]
INC
A2 DBAND (Alarm-2 Dead Band)
[0.0 ~ 10.0%F.S]
0
A2 TIME (Alarm-2 Time)
[0~ 60]SEC
1
DEVICE MODE
485 B/D
[CHECK / EMPTY]
ADDRESS
[0 ~ 64]
[1]
SENSOR MODE
Factory Setting
MAINTEN.MODE
Factory Setting
VERSION MODE
Factory Setting
TEST MODE
Factory Setting
■ After power on, it passes self-diagnostic process then enters Measuring Mode. Here, by operating front keys,
you can go to internal System Mode.
■ Timeout for Level1 and Level2 are 10 sec. It is set to 1 h for Level2 Calibration and Test Mode.
■ When "RESET: key contacts at Program Mode Screen, it returns to Measuring Mode. When "RESET" key contacts
at each Program Setting Screen, it returns to the parent step.