Function 

introduction 

Controller

function introduction

F-01  Address, Range1-200

F-02  Low point alarm

F-03  High point alarm

F-04  Zero calibration

F-05  4mA offset correction

F-06  ADC check

F-07  Standard gas concentration

F-08  Calibration switch

F-09  Production date

F-10  Reserved function

F-11  Serial communication check. 0 no check, 1 odd check, 2 even check F-12  

Arrangement mode of the floating-point data

0:DCBA

1:ABCD

2:CDAB
Need to press OK to save after all the above parameters are modified, which can take effect 

immediately, power outage restart also valid.

Installation Instruction

1. Location Selection

The location selection of the gas detection transmitter is essential to achieve the best detection results. In 

the selection of location, we need to consider the following factors: the density of gas in a leaking point, 

proportion of target gas, the impact of surrounding buildings, condition of production equipment, wind direction 

and annual meteorological conditions and even the location of windows and doors in an indoor environment.

We provide the following suggestions for your reference:

A. Maintain a proper distance between the detector and the possible gas leaking point. It would react too 

fast or too frequent if the distance is not enough, which may paralyze people's mind.

B. The detector must be located in the downwind of the possible leaking point.

C. If installed indoor, but the source of the leak is outdoor, the detector must be installed at the air inlet.
D. Determine the height according to proportion of target gas in air.
E. Determine the quantity of detectors according to the condition of possible leaking point, frequency 

of staff attendance and time of stay as well as the economic effect.

F. Consider to increase quantity of inspection point if the equipment is old.

G. Protect the detector from radiation of high temperature heart source. Environments of both 

very high temperature and very low temperature will affect the result and lifespan of the detector.

www.gasdog.com

[email protected]

+86 773-280-9002

9

Summary of Contents for 41547

Page 1: ...brand sensors and advanced micro process technology with data display fast response high preci sion and good stability Powered by 24V DC with 4 20mA RS485 relay signal output Explosion proof suitable...

Page 2: ...he specific gas concentration in environment or pipeline and alarm With self calibration and zero calibration function makes the detection more accurate and reliable With temperature compensation this...

Page 3: ...0 25 VOL 0 2000ppm 0 1000ppm 0 100 VOL 0 200ppm 0 100ppm 0 100ppm 0 40000ppm 0 250ppm 0 100ppm 0 2000ppm 0 100ppm 0 1000ppm 0 50000ppm 0 5000ppm 0 1000ppm 0 5000ppm 0 100ppm 0 90 VOL 0 50ppm 1 LEL 0...

Page 4: ...Interior Decoration and Renovation Dyestuff Papermaking Pharmacy Health Care Foodstuff Antiseptic Disinfection Chemical Fertilizer Resin Adhesive Pesticide Raw Material Sample Technological Process L...

Page 5: ...iability if users operate the repair of replacement by themselves E There is acid solution inside the transmitter please do not disassembleit And pay attention not to damage the frontal membrane of th...

Page 6: ...tion Ground connection port 5 6 1 2 3 4 7 NC Normally close NO Normally open COM Common 24V 24 positive GND 24 negative 4 20mA 4 20mA analog signal Low Alarm High Alarm Relay Relay Powered Signal outp...

Page 7: ...2 F S H2 2 F S CO2 2 F S C2H4 2 F S NO2 2 F S N2 2 F S TVOC 2 F S NH3 2 F S ASH3 2 F S C3H3N 2 F S F2 2 F S O3 2 F S CL2 2 F S BF3 Range 0 30 VOL 0 1000ppm 0 1000ppm 0 20000ppm 0 10000ppm 0 100ppm 0 2...

Page 8: ...ress to modify the value Press OK to save settings and BACK to cancel 3 Continue to press to enter F03 maximum value setting menu of gas alarm Press OK to modify press to modify the value Press OK to...

Page 9: ...pment wind direction and annual meteorological conditions and even the location of windows and doors in an indoor environment We provide the following suggestions for your reference A Maintain a prope...

Page 10: ...iable ground wire For the wire between the transmitter and the main engine the shorter the better And protect the wire with iron pipe Method of Calibration To guarantee the measurement accuracy of the...

Page 11: ...seconds then the instrument will be calibrated automatically The measured concentration value is consistent with the value set in F 07 4 After calibration left the detector in the air for a while Shut...

Reviews: