Preliminary Guidelines
4.6 Power Setup
Page 32
MDE-5411A ForeHB Islander Prime Installation Manual · October 2018
4.5.1 Cable Types
The following are the types of cables used for the wiring of the Islander Prime system
(see
):
Table 4:
No
.
Function
Type
1
AC Power from
Office
Power cable, 3x1.5 mm
2
0.118 x 0.06-inch
2
/ NYY (14 AWG), in accordance with local
standards.
Control to pumps
(valves or engine)
In-use signal
2
Coil (Barrier)
Data communication cable, 300 V RMS, 90°C /194°F, shielded twisted pair, oil resistant, 24
AWG, low capacitance below 60 PF/meter (3.3') similar to Belden 9729 cable.
Pulser
TLG (RS-232)
3
LAN
CAT5E, Shielded, 300 V RMS, 90°C/194°F similar to Belden 121700A.
4
GND
Ground cable 0.4-inch (10.8-mm
2
).
Islander Prime Cable Types
4.5.2 Cable Routing
Route the cables from the peripherals and the office to Islander Prime as shown below
(see
):
Table 5: Islander Prime Cable Routing
No.
Functional Description
From
Through Insert
Cable Type
1
Power AC
Office
High voltage conduit
1
2
GND
Office
High voltage conduit
4
3
TLG
Office
Low voltage conduit
2
4
LAN
Office
Low voltage conduit
3
5
Control, Pump A
Pump A
High voltage conduit
1
6
In-use, Pump A
Pump A
High voltage conduit
1
7
GND
Pump A
Low voltage conduit
2
Note: The cable type number refers to the table in the above section (see
4.6 Power Setup
The power equipment must be installed in the main power cabinet. It should include the
following:
• Mains Circuit Control (MCC) Box includes dedicated circuit breaker for the pedestal
• Uninterruptible Power Supply (UPS) - Online (“True”) UPS