MDE-4334C Atlas Start-up and Service Manual · April 2008
Page 5-11
Configuring the 9800 Series
Pump Programming
SW2-8 - Background Debug Module (BDM) Enable
(Only on M06333KXXXX CPU)
This switch must be OPEN for normal operation.
SW2-9 - Software Load Enable
(Only on M06333KXXXX CPU)
This switch must be OPEN for normal operation. When this switch is closed, it enables
loading the new M06333KXXXX CPU software.
SW2-10
(Only on M06333KXXXX CPU)
This switch is not used. Set to the Open position.
ATC Setup
When you activate the magnet located at the opposite side of the totalizer, the following items
appear on the display.
Display Name
Example
Display Description
Volume
0023043
Uncompensated volume
Probe Temperature
023.2
Probe temperature in Celsius only
Flow Rate
189.2
Flow rate (in LPM only)
Software Version
1.30
Software version number
ATC Status
842.2
Automatic Temperature Compensation
On the status display, the rightmost digit (2) indicates whether the temperature compression is
enabled or not, and if so, the product that is being dispensed. The following digits indicate the
settings that have been enabled:
• 0 = Temperature compensation enabled
• 1 = Product is gasoline and compensation is enabled
• 2 = Product is diesel and compensation is enabled
On the status display, the leftmost digits (842) are error indicators, which are blank when the
corresponding error condition is not active. When any of these digits are displayed, it indicates
the following:
• 8 = Temperature probe fault is detected
• 4 = Pulser error occurred
• 2 = Exceptional reset was detected