Magnum 10KG Managed Switch Installation and User Guide
07/12
45
www GarrettCom com
.
.
A3.1
UL Requirements for DC-powered units
CAUTION: 48VDC products shall be installed with a readily accessible
disconnect device in the building installation supply circuit to the product.
Minimum 18AWG cable for connection to a Centralized DC power source.
1.
Minimum 14AWG cable for connection to an earth wiring.
2.
Use only with Listed 10A circuit breaker provided in building installation.
3.
“Complies with FDA radiation performance standards, 21 CFR subchapter J.”
or equivalent.
4.
Fastening torque of the lugs on the terminal block: 9 inch-pound max.
5.
To secure a centralized DC Power Source cable , use at least four cable ties to
secure the cable to the rack at least 4 inches apart, with the first one located
within 6 inches of the terminal block.
A4.0 TROUBLESHOOTING
Please refer to Section 6.0 for troubleshooting.